§ 10.10.070: Fire hydrant location and number requirements.
A. The distance between fire hydrants in single-family zones shall be pursuant to IFC Section 507 and IFC Appendix C. B. The maximum distance between fire hydrants in other than single-family zones shall be pursuant to IFC Section 507 and IFC Appendix C. C. The length of any fire hydrant lead shall not exceed one hundred fifty feet. D. Not more than one fire hydrant shall be installed on a six-inch main between intersecting mains and not more than two fire hydrants shall be installed on an eight-inch line between intersecting mains.
( Ord. 1764 § 9 (part), 1975 ; Ord. 2176 § 3, 1978 ; Ord. 2354 § 21, 1979 ; Ord. 2006-07 § 66, 2006 ; Ord. 2024-007 § 2, 2024 )