Sec. 18-567. - Installation of pipes.

(a) Bending pipe. Rigid or hard tempered pipe shall not be bent. Fittings shall be used when making turns in rigid or hard tempered gas piping. (b) Location and size of drips. All drips shall be installed only in such locations that they will be readily accessible to permit cleaning and emptying. A drip shall not be located where the condensate is likely to freeze. The size of any drip shall be determined by the capacity and the exposure of the piping which drains to it and shall not be of smaller diameter than the pipe to which it is attached. (c) Use of tee. A tee fitting with the bottom outlet plugged or capped instead of an ell fitting shall be used as the bottom of any riser to catch any dirt or other foreign materials. (d) Branch pipe connections. All branch outlet pipes shall be taken from the top or sides of horizontal lines where possible. Where a branch outlet is placed on a main supply line before it is known what size of pipe will be connected to it, the outlet shall be of the same size as the line which supplies it.

(Ord. No. 07-16, 12-20-16)