§ 1517.03 — BURNERS
Codified Ordinances of the City of Huntington, West Virginia (Codified through Ordinance No. 2025-O-31, adopted September 22, 2025. (Supp. No. 8)) · Huntington Codified Ordinances § 1517.03
Corpus is an independent public-information project, not the official City of Huntington website. Stable reference: corpuslaw.us/code/a3c36366-bd3b-49cf-b43b-95abd7f6163c
1517.03 - BURNERS.
(a) Location. All gas burners shall be placed at least three feet below any woodwork or ceiling attached to wooden beams, unless the same is properly protected by a shield, in which case the distance shall be not less than 18 inches. (b) Pilot lights. Gas burners installed in low pressure steam boilers or hot water boilers or furnaces, used for heating buildings, shall be provided with a thermostatic pilot light so constructed and adjusted that no gas can flow through the main burner unless the pilot light is burning, or with some other similar type of safety device serving the same end. The operation of the safety device which shuts off the main gas supply shall not depend on the closing of an electric circuit.
(1964 Code Secs. 12-50, 12-51)