For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 1521.13 — MINIMUM AIR FLOW

Codified Ordinances of the City of Huntington, West Virginia (Codified through Ordinance No. 2025-O-31, adopted September 22, 2025. (Supp. No. 8)) · Huntington Codified Ordinances § 1521.13

Corpus is an independent public-information project, not the official City of Huntington website. Stable reference: corpuslaw.us/code/8dd2db55-b279-4c76-b4fe-beac4cfa6c51

1521.13 - MINIMUM AIR FLOW.

In order to minimize any solvent vapor build-up in the customer area of a self-service or coin-operated dry cleaning establishment, during business hours a minimum flow of air shall be maintained from the customer area through the partition at the following rate: Number of Machines | Minimum Flow Rate C.F.M. Per Machine 1—3 | 500 4—8 | 400 9—16 | 375 17 or more | 360 A general ventilation fan, capable of exhausting a minimum of 1,000 cubic feet per minute per machine, shall be installed in the exterior wall of the maintenance room. In case of a serious solvent leakage, such fan shall be operated at capacity level. Tempered make-up shall be provided in sufficient quantities to eliminate any negative pressure conditions that would otherwise develop as a result of air exhausted from the plant.

(1964 Code Sec. 12-71)

Ask a question about Huntington law

Corpus searches the Huntington sections it holds and shows the ones that match, with their citations. Free, no sign-in.