§ 14B-7-703 — Fire-resistance ratings and fire tests

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14B-7-703

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/05231431-b008-47a7-8937-fafdb4b762c6

14B-7-703 Fire-resistance ratings and fire tests.

The provisions of Section 703 of IBC are adopted by reference with the following modifications: 1. Delete Section 703.2.5. 2. Revise the numbered portion of Section 703.3 to read: "1. Fire-resistance designs documented in a test report prepared by an approved agency or test results compiled in the UL Online Certifications Directory, Intertek Directory of Building Products, GA 600 or another approved source. 2. Prescriptive designs of fire-resistance-rated building elements, components or assemblies as prescribed in Section 721. 3. Approved calculations in accordance with Section 722. 4. Approved engineering analysis based on a comparison of building element, component or assembly designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E119 or UL 263." 3. Delete the last sentence of Section 703.4. 4. Revise the first sentence of Section 703.7 to read: "Where there is an accessible concealed floor, floor-ceiling or attic space and within mechanical and electrical rooms, fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other wall required to have protected openings or penetrations shall be effectively and permanently identified with signs or stenciling in the concealed space or mechanical or electrical room."

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.