Sec. 29-85. - Grease and hair traps/interceptors and sample wells.
(a) Commercial laundry equipment and commercial and industrial buildings that discharge grease, fatty materials and/or lint, shall install an approved interceptor with a sample well. Before the issuance of any permit for such work, two sets of plans showing location, related piping riser diagram and manufacturer specification sheet for the specific model interceptor to be installed must be submitted for review and approved by the plumbing and health departments.
(b) Oil and sand separators-interceptors. All repair garages, auto dealer service areas and businesses which have oily, flammable or both types of waste as a result of manufacturing, storage, maintenance, repair or testing processes shall have one hundred (100) per cent recovery and meet one of the criteria set forth by the administration having jurisdiction. Prior to the opening of or permitting of any such business or work, a set of engineered plans showing the layout of the drainage system, the manufacturers specifications and the manufacturer's installation instructions for the separator shall be submitted to the health and plumbing departments for plan review. All separators shall be installed per manufacturer instructions and inspected.
(c) Design of separators/interceptors. Separators, interceptors shall be rated and labeled and designed for the load they are designed for.
(d) Sample wells when required. Sample wells will be required at food preparation facilities, food processing plants, auto repair shops, lubrication centers for autos, film processing establishments, beauty salons, strip centers, hospitals, chemical companies, chemical handlers, chemical suppliers, chemical manufacturers, any facility that requires a grease trap or separator or anywhere the authority having jurisdiction has deemed necessary. If a building has more than one (1) sewer tap then each line shall have a sample well.
(e) Sample well installation. Sample wells shall be installed as close as possible to the building it serves. If the sewer line is six (6) feet (one thousand eight hundred thirty (1,830) mm) or less, then the sample well shall have a diameter of fifteen (15) inches (three hundred eighty-one (381) mm) deeper than six (6) feet the sample well shall have a diameter of twenty-four (24) inches (six hundred ten (610) mm).
(f) Hair traps. An approved listed hair trap shall be installed on drains for shampoo bowls and any other similar fixtures for human or non-human use, such as but not limited to sinks, tubs or showers for the purposes of washing animals.
(Ord. No. 17-009, § 1(Exh. A), 1-17-17)