Omaha Municipal Code § 49-1210 Drains and scuppers overflow.
Sec. 49-1210. - Drains and scuppers overflow.
Where roof drains are required, overflow drains having the same size as the roof drains (or overflow scuppers having three times the size of the roof drains) shall be installed. See exceptions section 49-1211.
The following provisions shall also be observed:
(a) The inlet flow line shall be located two inches above the low point of the roof. (See Figure 49-1210(a).)
(b) Overflow scuppers three times the roof drains' size may be installed in adjacent parapet walls with the inlet flow line located a maximum of two inches above the low point of the adjacent roof and having a minimum opening height of four inches. (See Figures 49-1210(a) and 49-1210(b).)
(c) Overflow drains:
(1) Shall be connected to piping that is independent of the roof drain piping system and shall be discharged to daylight no more than of 18 inches above grade (see Figure 49-1210(c)); or
(2) Shall be connected to the building storm sewer after first passing through an area inlet or manhole with a grated cover within 15 feet of the building (see Figure 49-1210(c)(2)).
(Ord. No. 40524, § 1, 10-20-15)