§ 57.2404.7.9.1 — GAUGE OF METAL
Los Angeles Municipal Code (2026 Rev. 9, current through legislation effective June 30, 2026) · Los Angeles Municipal Code § 57.2404.7.9.1
Corpus is an independent public-information project, not the official City of Los Angeles website. Stable reference: corpuslaw.us/code/0e6b5121-2151-41a3-bffd-84a9de6df384
SEC. 57.2404.7.9.1. GAUGE OF METAL.
Every duct or pipe shall be constructed of galvanized metal sheets in accordance with the provisions of Table 57.2404.7.9.1. TABLE 57.2404.7.9.1 SPRAY EXHAUST DUCTS – GAUGE OF METAL Duct Cross-Sectional Dimension in Inches | Gauge of Duct Metal Up to 8 | 24 Over 8 inches to 18 | 22 Over 18 inches to 30 | 20 Over 30 | 18
Ask a question about Los Angeles law
Corpus searches the Los Angeles sections it holds and shows the ones that match, with their citations. Free, no sign-in.