Sec. 12-73. - Minimum wiring methods in residential occupancies.
General purpose and lighting branch circuits shall be rated a minimum of twenty (20) amperes (twenty (20) amp breakers; no. 12 AWG conductors). Each such circuit shall not serve over twelve (12) outlets. For this purpose an outlet is a duplex or single receptacle or a luminaire.
(Ord. No. 17-009, § 1(Exh. A), 1-17-17)