Underground storage tanks for regulated substances.
Minneapolis Code of Ordinances § 48.130
in effect48.130. - Underground storage tanks for regulated substances.
(a) Prior to beginning installation of any underground storage tank regulated by the state, owner and operators must notify the authority of their intent to install the underground storage tank system and pay a filing fee required by section 48.310. Notification can be a copy of the state form, or the city supplied form. Notification must include type of tank system to be installed, method of cathodic protection, and release detection and site plan.
(b) Prior to beginning either removal, abandonment, or switching the stored material to or from a regulated substance, owners and operators of an underground tank must notify the authority of their intent to remove, abandon or change-in-service, and pay a filing fee required by section 48.310.
(c) Upon underground storage tank removal or abandonment, all associated fill, vent, and product lines must be removed, or properly abandoned in place if inaccessible, regardless of tank size or use. Exceptions to this requirement are tanks that are being replaced within thirty (30) days and if lines meet current federal requirements for product lines.
(d) Authority shall have the right to inspect all tank locations before, during, and after installation, removal, or abandonment. Applicant shall notify the authority prior to installing, removing, or abandoning any underground storage tank to arrange a site inspection. (2000-Or-017, § 1, 4-7-00; 2002-Or-169, §§ 8, 9, 11-8-02; Ord. No. 2016-026, § 15, 4-1-16)
Source: City of Minneapolis, Minnesota, Code of Ordinances, City Charter and Park and Recreation Board Code of Ordinances (Municode Library, library.municode.com)URL: https://library.municode.com/mn/minneapolis/codes/code_of_ordinances?nodeId=COOR_TIT3AIPOENPR_CH48MIWAMAAU_48.130UNSTTARESUFetched: 11/2/2026