Location of public and private well sites.
Round Rock Code of Ordinances § 14-58
in effectSec. 14-58. - Location of public and private well sites.
(a) Water wells shall be so located to protect the water supply of the well by means of sanitary control and shall be so located that there will be no danger of pollution from flooding or from unsanitary surroundings, such as cesspools, privies, sewage, livestock and animal pens, solid waste disposal sites, or abandoned and improperly sealed wells.
(b) The construction and operation of underground petroleum and chemical storage tanks and liquid transmission pipelines, stock pens, feedlots, dump grounds, privies, cesspools, septic tank or sewage treatment drainfields, improperly constructed water wells of any depth, and all other construction or operation that could create an unsanitary condition is prohibited within a 150-foot radius of a public water well. For the purpose of this subsection, improperly constructed public water wells are those wells which do not meet the surface and subsurface construction standards for a public water well.
(c) The construction of tile or concrete sanitary sewers, sewer appurtenances, septic tanks, storm sewers, and cemeteries is prohibited within a 50-foot radius of a public water well.
(d) No well site shall be located or selected which is within 500 feet of a sewage treatment plant or within 300 feet of a sewage wet well, sewage pumping station, or a drainage ditch which contains industrial waste discharges or the wastes from sewage treatment systems.
(e) No water wells shall be located within 500 feet of animal feed lots, solid waste disposal sites, lands on which sewage plant or septic tank sludge is applied, or lands irrigated by sewage plant effluent.
(f) Livestock in pastures shall not be allowed within 50 feet of a water well.
(g) All known abandoned or inoperative wells (unused wells that have not been plugged) within one-quarter mile of a proposed well site shall be reported to the city and the Texas Commission on Environmental Quality along with existing or potential pollution hazards. This information must be submitted prior to construction.
(Code 1995, § 6.304; Ord. No. G-03-11-25-11E1, 11-25-2003)
Source: City of Round Rock, Texas, Code of Ordinances (Municode Library, library.municode.com)URL: https://library.municode.com/tx/round_rock/codes/code_of_ordinances?nodeId=PTIICOOR_CH14EN_ARTIIIPUPRWAWE_S14-58LOPUPRWESIFetched: 11/16/2026