Sec. 10-52. - Amendments to the adopted chapters of the National Electrical Code (2023).
Additions to the National Electrical Code (NEC) are shown as underlined text. Deletions of the NEC are shown as bracketed [strikethroughs].
Article 100, Definitions, is amended for Dwelling Unit to read as follows:
Dwelling Unit. A single unit, providing complete and independent living facilities for one or more persons, including permanent provisions for living, sleeping, cooking and sanitation to include free-standing habitable structures at dwellings.
Article 200.6, Means of Identifying Grounded Conductors, paragraphs (A), (A)(1), (A)(2), A (3) and paragraphs (B), (B)(1), (B)(2), (B)(3) and (B)(4) are amended as follows, with all other Code text remaining as is:
200.6. Means of Identifying Grounded Conductors.
(A) Sizes 10 [6] AWG or Smaller. The insulation of grounded conductors of 10 [6] AWG or smaller shall be identified by one of the following means:
(A) (1) A continuous white outer finish shall be used on all systems with a voltage of less than 150 Volts between the grounded and ungrounded conductors.
(A) (2) A continuous gray outer finishshall be used on all systems with a voltage of 150 Volts or higher between the grounded and ungrounded conductors.
[(A) (3) [Three continuous white or gray stripes along the conductor's entire length on other than green insulation.]
(B) Sizes 8 [4] AWG or Larger. An insulated grounded conductor 8 [4] AWG or larger shall be identified by one of the following means:
(B) (1) A continuous white outer finish shall be used on all systems with a voltage of less than 150 Volts between the grounded and ungrounded conductors.
(B) (2) A continuous gray outer finish shall be used on all systems with a voltage of 150 Volts or higher between the grounded and ungrounded conductors.
[(B) (3) Three continuous white or gray stripes along the conductor's entire length on other than green insulation.]
(B) (3) [(4)] At the time of installation, be identified by a distinctive white or gray marking tape at its terminations. The [This] marking tape shall encircle the conductor insulation a minimum of two inches in length.
Article 200.7, Use of Insulation of a White or Gray Color or with Three Continuous White or Gray Stripes, is amended just on the title as follows; all other Code text remains as is:
200.7 Use of Insulation of a White or Gray Color or with Three Continuous White or Gray Stripes on Cables Listed in Article 334.
Article 210.5, Identification for Branch Circuits, paragraphs (C)(1)(a), (C)(2), (C)(2)(a) and (C)(2)(b) are amended as follows, all other Code text remains as is:
210.5 Identification for Branch Circuits.
(C) Identification of Ungrounded Conductors. Ungrounded conductors shall be identified in accordance with 210.5(C)(1) or (2), as applicable.
(1) Branch Circuits Supplied from More Than One Nominal Voltage System. Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit shall be identified by phase or line and by nominal voltage system at all termination, connection, and splice points in accordance with 210.5(C)(1)(a) and (C)(1) (b). Different systems within the same premises that have the same nominal voltage shall be permitted to use the same identification.
(a) Means of Identification. Conductors 10 AWG and smaller shall have factory colored insulation. Conductors 8 AWG and larger may have factory colored insulation or black insulation with a marking tape that encircles the insulation a minimum of two inches in length. Color of insulation or marking tape shall comply with the following table: [The means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means.]
Exception: Where #10 or smaller NM cable where the white or gray "grounded" conductor is used as a phase conductor, it shall be permitted to be field-marked with the required phase conductor color, throughout the entire visible length in disconnects, junction boxes, panels, and termination points. No white or gray insulation color shall be visible.
UNGROUNDED CONDUCTOR IDENTIFICATION COLORS FOR ELECTRICAL SYSTEMS
208Y/120 Volts | 120/240 Volts | 480Y/277 Volts | 120/240 Volts
A - Black | A - Black | A - Purple | A - Black
B - Red | B - Orange (high leg) | B - Brown | B - Red
C - Blue | C - Blue | C - Yellow
Informational Note 1: Conductors used for switch legs shall be the same color as the branch circuit conductors.
Informational Note 2: Conductors used for travelers may be of the same color as its associated switch leg or may be any of the above colors not used on the project. The colors designated for the grounded conductor, grounding conductors or for identification of the high leg may not be used for travelers.
Informational Note 3: In existing installations where modifications to the electrical system are required, and there is an established system of colors for ungrounded conductors, the existing color-coding system may continue to be used.
(2) Branch Circuits Supplied from Direct-Current Systems. Where a branch circuit is supplied from a dc system operating at more than 60 volts, each ungrounded conductor of 8 [4] AWG or larger shall be identified by polarity at all termination, connection, and splice points by marking tape, tagging, or other approved means; each ungrounded conductor of 10 [6] AWG or smaller shall be identified by polarity at all termination, connection, and splice points in compliance with 210.5(C)(2)(a) and (b). The identification methods utilized for conductors originating within each branch-circuit panelboard or similar branch-circuit distribution equipment shall be documented in a manner that is readily available or shall be permanently posted at each branch-circuit panelboard or similar branch-circuit distribution equipment.
(a) Positive Polarity, Sizes 10 [6] AWG or Smaller. Where the positive polarity of a dc system does not serve as the connection point for the grounded conductor, each positive ungrounded conductor shall be identified by one of the following means:
* * * * *
(b) Negative Polarity, Sizes 10 [6] AWG or Smaller. Where the negative polarity of a dc system does not serve as the connection point for the grounded conductor, each negative ungrounded conductor shall be identified by one of the following means:
Article 210.8, Ground-Fault Circuit-Interrupter Protection for Personnel, paragraph (B)Other Than Dwelling Units, is amended to add Number 16, all other code text remains as is:
(B) Other Than Dwelling Units. All 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, and all receptacles supplied by three-phase branch circuits rated 150 volts or less to ground, 100 amperes or less, installed in the following locations shall be provided with GFCI protection.
(16) Aircraft hangar
Article 210.23, Permissible Loads, Multiple-Outlet Branch Circuits, paragraph (A) 10-Ampere Branch Circuits, is deleted as follows, all other code text remains as is:
[ (A) 10-Ampere Branch Circuits. A 10-ampere branch circuit shall comply with the requirements of 210.23(A)(1) and (A)(2).
(1) Load Permitted for 10-Ampere Branch Circuits. A 10-ampere branch circuit shall be permitted to supply one or more of the following:
(1) Lighting outlets
(2) Dwelling unit exhaust fans on bathroom or laundry room lighting circuits
(3) A gas fireplace unit supplied by an individual branch circuit
(2) Loads Not Permitted for 10-Ampere Branch Circuits. A 10-ampere branch circuit shall not supply any of the following:
(1) Receptacle outlets
(2) Fixed appliances, except as permitted for individual branch circuits
(3) Garage door openers
(4) Laundry equipment]
Article 210.52, Dwelling Unit Receptacle Outlets, paragraph (B)(1) and (C)(2) are amended as follows, all other code text remains as is:
(B) Small Appliances.
(1) Receptacle Outlets Served. In the kitchen, pantry, breakfast room, dining room, or similar area of a dwelling unit, the two or more 20-ampere small-appliance branch circuits required by 210.11(C)(1) shall serve all wall and floor receptacle outlets covered by 210.52(A), and all countertop outlets covered by 210.52(C) [, and receptacle outlets for refrigeration equipment]. Receptacle outlets for refrigeration equipment shall not be connected to the small- appliance branch circuits.
(C) Countertops and Work Surfaces.
(2) Island and Peninsular Countertops and Work Surfaces. Receptacle outlets, if installed to serve an island or peninsula countertop or work surface, shall be installed in accordance with 210.52(C)(3). [If a receptacle outlet is not provided to serve an island or peninsular countertop or work surface, provisions shall be provided at the island or peninsula for future addition of a receptacle outlet to serve the island or peninsular countertop or work surface.]
Article 210.70, Lighting Outlets Required, is amended to include 210.70(D); all other code text remains as is:
210.70 Lighting Outlets Required. Lighting outlets shall be installed where specified in 210.70(A), (B), [and] (C), and D. The switch or wall-mounted control device shall not rely exclusively on a battery unless a means is provided for automatically energizing the lighting outlets upon battery failure.
(D) Open Lamps. Lighting outlets required by 210.70(A)(3) and 210.70(C) with open lamps shall be guarded where installed less than seven feet above the working surface measured directly below the lamp or where exposed to physical damage.
Article 215.12, Identification for Feeders, paragraphs (C)(1)(a), (C)(2), (C)(2)(a) and (C)(2)(b) are amended to read as follows:
215.12 Identification for Feeders.
(C) Identification of Ungrounded Conductors. Ungrounded conductors shall be identified in accordance with 215.12(C)(1) or (C)(2), as applicable.
(1) Feeders Supplied from More Than One Nominal Voltage System. Where the premises wiring system has feeders supplied from more than one nominal voltage system, each ungrounded conductor of a feeder shall be identified by phase or line and system at all termination, connection, and splice points in compliance with 215.12(C)(1)(a) and (C)(1)(b).
(a). Means of Identification. Feeders shall be color coded in accordance with Article 210.5(C)(1)(a). [The means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means.]
(2) Feeders Supplied from Direct-Current Systems. Where a feeder is supplied from a dc system operating at more than 60 volts, each ungrounded conductor of 8 [4] AWG or larger shall be identified by polarity at all termination, connection, and splice points by marking tape, tagging, or other approved means; each ungrounded conductor 10 [6] AWG or smaller shall be identified by polarity at all termination, connection, and splice points in compliance with 215.12(C)(2)(a) and (C)(2)(b). The identification methods utilized for conductors originating within each feeder panelboard or similar feeder distribution equipment shall be documented in a manner that is readily available or shall be permanently posted at each feeder panelboard or similar feeder distribution equipment.
(a). Positive Polarity, sizes 10 [6] AWG or Smaller. Where the positive polarity of a dc system does not serve as the connection for the grounded conductor, each positive ungrounded conductor shall be identified by one of the following means:
* * * * *
(b). Negative Polarity, sizes 10 [6] AWG or Smaller. Where the negative polarity of a dc system does not serve as the connection for the grounded conductor, each negative ungrounded conductor shall be identified by one of the following means:
* * * * *
Article 220.41, Dwelling Units, Minimum Unit Load, is amended as follows, all other code text remains as is:
220.41 Dwelling Units, Minimum Unit Load. In one-family, two-family, and multifamily dwellings, the minimum unit load shall be not less than 33 volt-amperes/m 2 (3 volt-amperes /ft 2 ). Unit loads include the following lighting and receptacle outlets, and no additional load calculations shall be required.
(1) All general-use receptacle outlets of 20-ampere rating or less, including receptacles connected to the circuits specified in 210.11(C)(3) and (C)(4)
(2) The receptacle outlets specified in 210.52(E) and (G)
(3) The lighting outlets specified in 210.70
The minimum lighting load shall be determined using the minimum unit load and the floor area as determined in 220.5(C) for dwelling occupancies. Motors rated less than 1/8 hp and connected to a lighting circuit shall be considered part of the minimum lighting load. A maximum load of 1440 VA, consisting of receptacles at 180 VA each plus luminaires at their maximum allowed lamp wattage shall be permitted on a 15 A branch circuit and a maximum load of 1920 VA, consisting of receptacles at 180 VA each plus luminaires at their maximum allowed lamp wattage shall be permitted on a 20 A branch circuit. When using the optional VA method in lieu of the total number of outlets described in the previous sentence, the VA load shall be computed in accordance 210.20(A) - receptacles at 100% plus luminaires at 125%.
Article 225.30(B), Common Supply Equipment, is repealed in its entirety.
Article 230.2, Number of Services, paragraph (F) and (G) are added as follows, all other code text remains as is:
230.2 Number of Services. A building or other structure served shall be supplied by only one service unless permitted in 230.2(A) through (G) [(D)]. For the purpose of 230.40, Exception No. 2 only, underground sets of conductors, 1/0 AWG and larger, running to the same location and connected together at their supply end but not connected together at their load end shall be considered to be supplying one service.
(F) Color Coding. Service entrance conductors shall be color coded in accordance with Article 210.5(C)(1)(a).
(G) Fire Barrier Separation. A minimum two-hour fire barrier is required to separate the areas served by each service. The fire barrier shall be constructed per the International Building Code. Electrical wiring in buildings with multiple services shall not cross the fire barrier.
Exception No. 1: A fire barrier is not required where an additional service is permitted by CPS Energy to supply legally required fire pumps.
Exception No. 2. A fire barrier is not required where separate services are permitted in accordance with Article 206.1 of the CPS Energy Standards and all service disconnecting means can be grouped together in a manner approved by CPS Energy. In no case shall grouped service disconnects exceed six handles.
Article 230.30, Installation, paragraph (B) is amended as follows, all other code text remains as is:
230.30 Installation.
(B) Wiring Methods. Underground service conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and shall be limited to the following methods as modified below:
(1) RMC conduit
(2) IMC conduit
(3) Type NUCC conduit - encased in controlled low strength material (CLSM)
(4) HDPE conduit - encased in controlled low strength material (CLSM)
(5) PVC conduit - encased in controlled low strength material (CLSM)
(6) RTRC conduit - encased in controlled low strength material (CLSM)
(7) Type IGS cable
(8) Type USE conductors or cables
(9) Type MV or Type MC cable identified for direct burial applications
(10) Type MI cable, where suitably protected against physical damage and corrosive conditions.
(11) Type TC-ER cable where identified for service entrance use and direct burial applications.
Where encasement is required above, it shall be a minimum 75 mm (3 in.) thick controlled low strength material envelope for new construction and additions.
Article 230.82, Equipment Connected to the Supply Side of Service Disconnect, is amended as follows, all other code text remains as is:
230.82 Equipment Connected to the Supply Side of Service Disconnect. Only the following equipment shall be permitted to be connected to the supply side of the service disconnecting means:
(5) Conductors used to supply energy management systems, circuits for standby power systems, fire pump equipment, and fire and sprinkler alarms, if provided with service equipment and install in accordance with requirements for service-entrance conductors. Such connections shall not be made within service equipment enclosures.
(6) Solar photovoltaic systems, fuel cell systems, wind electric systems, energy storage systems, or interconnected electric power production sources, if provided with a disconnecting means listed as suitable for use as service equipment, and overcurrent protection as specified in Part VII of Article 230. Such connections shall not be made within service equipment enclosures.
Article 240.4, Protection of Conductors, paragraph (B) is amended as follows, all other code text remains as is:
240.4 Protection of Conductors
(B) Overcurrent Devices Rated 800 Amperes or Less.
* * * * *
[If the overcurrent protection device is an adjustable trip device installed in accordance with 240.4(B)(1), (B)(2), and (B)(3), it shall be permitted to be set to a value that does not exceed the next higher standard value above the ampacity of the conductors being protected as shown in Table 240.6(A) where restricted access in accordance with 240.6(C) is provided.]
Article 240.24, Location in or on Premises, paragraph (D) is amended as follows, all other code text remains as is:
240.24 Location in or on Premises.
(D) Not in Vicinity of Easily Ignitable Material. Newly installed [O]overcurrent protection devices shall not be located in the vicinity of easily ignitable material, such as in clothes closets, storage rooms, janitor rooms, and similar. Replacements per the International Existing Building Code are permitted in existing location.
Article 250.52, Grounding Electrodes, paragraphs (A)(3)(1) and (A)(5)(2) are amended as follows, all other code text remains as is:
250.52 Grounding Electrodes.
(A) Electrodes Permitted for Grounding.
(3) Concrete-Encased Electrode. A concrete-encased electrode shall consist of at least 6.0 m (20 ft) of either of the following:
(1) One or more bare or zinc galvanized or other electrically conductive coated rebar of not less than 13 mm (1/2 in.) in diameter, installed in one continuous 6.0 m (20 ft) length, or if in multiple pieces, the rebar shall be connected together by steel tie wires, exothermic welding, welding, or other effective means to create a 6.0 (20 ft) or greater length
Informational Note to (A)(3)(1): A piece of reinforcing steel conforming to (1) above which has additional length, without splice, extended up past the sole plate of the structure to which the grounding electrode may be connected to and extended to the service equipment is acceptable. The portion of the reinforcing steel extending above the sole plate shall be painted green and the paint removed from the bar where the connection is made to the grounding electrode conductor.
(5) Rod and Pipe Electrodes. Rod and pipe electrodes shall not be less than 2.44 m (8 ft) in length and shall consist of the following materials.
(2) Rod-type grounding electrodes of stainless steel and copper or zinc coated steel shall be at least 15.87 mm (⅝ in.) in diameter [, unless listed].
Article 250.118, Types of Equipment Grounding Conductors, paragraph (A) is amended as follows, all other code text remains as is:
250.118 Types of Equipment Grounding Conductors.
(A) Permitted. As a minimum, the equipment grounding conductor shall consist of a conductor as described in item (1) as follows and may be supplemented by any of the other means described in items (2) through (14) as follows: [Each equipment grounding conductor run with or enclosing the circuit conductors shall be one or more or a combination of the following:]
Article 250.119, Identification of Wire-Type Equipment Grounding Conductors, paragraphs (B), (B)(1) and its Exception and (B)(2)c are amended as follows, all other code text remains as is:
250.119 Identification of Wire-Type Equipment Grounding Conductors.
(B) Conductors 8[4] AWG and Larger. Equipment grounding conductors 8 [4] AWG and larger shall comply with the following:
(1) At the time of installation, if the insulation does not comply with 250.119(A), it shall be permanently identified as an equipment grounding conductor at each end and at every point where the conductor is accessible.
Exception: Conductors 8 [4] AWG and larger shall not be required to be marked in conduit bodies that contain no splices or unused hubs.
(2) Identification shall encircle the conductor and shall be accomplished by one of the following:
c. Marking the insulation or covering with green tape, a minimum of two inches in length, or green adhesive labels at the termination
Article 250.120, Equipment Grounding Conductor Installation, is amended as follows:
250.120 Equipment Grounding Conductor Installation. An equipment grounding conductor shall be installed in accordance with 250.120 (A), (B), and (C). In one- and two-family dwellings, replacement of a panel will require that the feeder include separate grounded and grounding conductors, unless the 2-wire system is still in place throughout the dwelling(s) or if 3 wire receptacles have been installed in compliance with 250.130C or 406.4D(2)(b) or (c).
Article 314.19, Boxes Enclosing Flush Devices or Flush Equipment, is amended as follows:
314.19 Boxes Enclosing Flush Devices or Flush Equipment. Boxes used to enclose flush devices or flush equipment shall be of such design that the devices or equipment will be completely enclosed on the back and sides, and substantial support for the devices or equipment will be provided. Screws for supporting the box shall not also be used to attach a device or equipment. Boxes for flush devices or equipment shall have a minimum volume of 221 cm3(13.5 in.3).
ARTICLE 330.6, Listing Requirements, is amended as follows:
330.6 Listings Requirements. Type MC cable shall be listed. Fittings used for connecting type MC cable to boxes, cabinets, or other equipment shall be listed and identified for such use. Additionally, all fittings shall be equipped with an anti-shorting bushing.
Article 330.112, Insulation, is amended as follows with all other code provisions (A & B) remaining as is:
330.112 Insulation. Insulated conductors shall comply with 330.112(A) or (B) and shall be color coded per the requirements of this chapter.
Article 330.116, Sheath, is amended as follows:
330.116 Sheath. Metallic covering shall be one of the following types: smooth metallic sheath, corrugated metallic sheath, or interlocking metal tape armor. The metallic sheath shall be continuous and close fitting. A nonmagnetic sheath or armor shall be used on single conductor Type MC. Supplemental protection of an outer covering of corrosion-resistant material shall be permitted and shall be required where such protection is needed. The sheath shall not be used as a current-carrying conductor. The cutting of the interlocking metal tape armor shall be performed with an approved rotary cutting tool designed for cutting MC cable.
Article 406.12, Tamper-Resistant Receptacles, is amended to include 406.12 (11) and (12); all other code text remains as is:
(11) Public areas of assembly occupancies where children might be present
(12) All areas accessible to patients
Article 408.30, General, is amended as follows:
408.30 General. All panelboards shall have a rating not less than the minimum feeder capacity required for the load calculated in accordance with Part III, IV, or V of Article 220, as applicable. Panelboards containing the 120 Volt branch circuits serving the interior of one- and two-family dwelling units shall be located in the interior of the structure in a readily accessible location.
Article 410.36, Means of Support, (B) Suspended Ceilings is amended as follows; All other code text remains as is:
410.36 Means of Support.
(B) Suspended Ceilings. Framing members of suspended ceilings systems used to support luminaires shall be securely fastened to each other and shall be securely attached to the building structure at appropriate intervals. Luminaires shall be securely fastened to the ceiling framing member by mechanical means such as bolts, screws, or rivets. Listed clips identified for use with the type of ceiling framing members(s) and luminaire(s) shall also be permitted. Two independent support wires per luminaire on opposing corners shall be permitted when installed in accordance with 300.11(B).
Article 440.8, Single Machine and Location, is amended as follows:
440.8 Single Machine and Location. An air-conditioning or refrigerating system shall be considered to be a single machine under the provisions of 430.87, Exception No. 1, and 430.112, Exception. The motors shall be permitted to be located remotely from each other. Air-conditioning and refrigeration equipment shall not be installed within a zone measured 900 mm (3 ft) horizontally and 2.5 m (8 ft) vertically from the top of a bathtub rim or shower stall threshold unless fully concealed above the ceiling. The zone shall be all-encompassing and include the space directly over the tub or shower stall.
Article 445.18, Disconnecting Means, (A) Disconnecting Means is amended as follows; All other code text remains as is:
(A) 445.18 Disconnecting Means. Generators other than cord-and-plug-connected portable generators shall have one or more disconnecting means. Each disconnecting means shall simultaneously open all associated ungrounded conductors. Each disconnecting means shall be lockable open in accordance with 110.25.
[The disconnecting means shall be permitted to be located within the generator behind a hinged cover, door, or enclosure panel. Where the generator disconnecting means is located within the generator, a field applied label meeting the requirements of 110.21(B) shall be provided indicating the location of the generator disconnecting means.]
Article 517.6, Patient Care-Related Electrical Equipment, is amended as follows:
517.6 Patient Care-Related Electrical Equipment. The reconditioning requirements of this Code shall not apply to patient care-related electrical equipment.
Exception: Temporary equipment.
Article 517.10, Applicability, (B) Not Covered is amended as follows; All other code text remains as is:
517.10 Applicability.
(B) Not Covered. Part II shall not apply to the following:
(3) Areas used exclusively for any of the following purposes:
a. Intramuscular injections (immunizations)
b. Psychiatry and psychotherapy
c. Alternative medicine
[d. Optometry]
d [e]. Pharmacy services not contiguous to health care facilities
Article 525.20, Wiring Methods, (B) Single-Conductor is amended as follows; All other code text remains as is:
525.20 Wiring Methods.
(B) Flexible Cords and Single-Conductor Cables. Flexible cords shall be permitted only in sizes 12 AWG or larger and shall contain a separate grounding conductor. A maximum of one 25-foot (7.65 m) extension cord may be connected to each individual receptacle provided as part of the manufacturers listed generator. Single-conductor cable shall be permitted only in sizes 2 AWG or larger.
Article 604.10, Uses Permitted, Exception No. 1, is amended as follows, All other code text remains as is:
604.10 Uses Permitted.
Exception No. 1: In concealed spaces, one end of tapped cable shall be permitted to extend into hollow walls of manufactured wall systems, with removable panels for access to the wiring system, for direct termination at switch and outlet points.
Article 680.23, Underwater Luminaires, (A)General (4) is amended as follows; All other code text remains as is:
680.23 Underwater Luminaires.
(A) General.
(4) Voltage Limitation. No luminaires shall be installed for operation on supply circuits over 150 volts between conductors and the limits are 15 volts ac or 30 volts dc at the luminaire.
Article 701.4, Capacity and Rating, paragraph (D)(2) is amended as follows, All other code text remains as is:
701.4 Capacity and Rating.
(D) Parallel Operation. Parallel operation shall comply with Part I or Part II of Article 705 where the legally required source capacity required to supply the legally required load is maintained at all times. Parallel operation of the legally required source(s) shall consist of the sources specified in 701.4 (D)(1) and (D)(2).
(2) Alternate Source. Legally required standby sources shall be permitted to operate in parallel where the necessary equipment to establish and maintain a synchronous condition is provided. For paralleling electric generators or auxiliary power supplies, including emergency electric generators or auxiliary power supplies, the transfer scheme shall parallel no more than one (1) second with CPS Energy's distribution system during the transfer of the load from emergency/standby power to normal power. Such distributed generation systems shall be approved by CPS Energy's Distributed Generation section.
Article 705.50, System Operation, is amended to read as follows:
705.50 System Operation. Interconnected microgrid systems shall be capable of operating in interactive mode with a primary source of power, or electric utility, or other electric power production and distribution network. Microgrid systems shall be permitted to disconnect from other sources and operate in island mode only during the loss of utility power to act as a backup power source.
Article 706.7, Commissioning and Maintenance, (A) Commissioning is amended as follows; All other code text remans as is:
(A) Commissioning. ESSs shall be commissioned upon installation. Commissioning for one-and-two family dwellings shall be conducted by CPS Energy. [This shall not apply to one-and-two family dwellings.]
(Ord. No. 2025-01-30-0075, § 1(Att. 1), 1-30-25)