18.71.060 - Dynamic lateral analysis procedure.
A. General. Structures shall be analyzed for seismic forces acting concurrently on the orthogonal axes of the structure. The effects of the loading on two orthogonal axes shall be combined by the square root of the sum of the squares (SRSS) methods. B. Ground motion. The seismic ground motion values shall be determined in accordance with ASCE 7-16 and may be one of the following: 1. The elastic design response spectrum shall be seventy-five percent (75%) of the response spectrum described in ASCE 7-16 Section 11.4.6. 2. A site-specific response spectrum shall be seventy-five percent (75%) of the site-specific response spectrum described in ASCE 7-16 Section 11.4.8. C. Mathematical model. The three-dimensional mathematical model of the physical structure shall represent the spatial distribution of mass and stiffness of the structure to an extent which is adequate for the calculation of the significant features of its dynamic response. All concrete and masonry elements shall be included in the model of the physical structure. EXCEPTION: Concrete or masonry partitions that are adequately isolated from the concrete frame members and the floor above. Cast-in-place reinforced concrete floors with span-to-depth ratios less than three (3) to one (1) may be idealized as rigid diaphragms. Other floors, including floors constructed of precast elements with or without a reinforced concrete topping in conformance with ASCE 7-16 Section 12.3.1.3 may be idealized as flexible diaphragms. All other floors not permitted to be idealized as rigid or flexible diaphragms shall be analyzed considering the effective in-plane stiffness of the diaphragm, including effects of cracking and discontinuity between precast elements, as described in ASCE 7-16 Section 12.3.1. Ramps that interconnect floor levels shall be modeled as having mass appropriately distributed on that element. The lateral stiffness of the ramp may be calculated as having properties based on the uncracked cross section of the slab exclusive of beams and girders. D. Effective stiffness. 1. General. The effective stiffness of concrete and masonry elements or systems shall be calculated as the secant stiffness of the element or system with due consideration of the effects of tensile cracking and compression strain. The secant stiffness shall be taken from the force-displacement relationship of the element or system. The secant stiffness shall be measured as the slope from the origin to the intersection of the force-displacement relationship at the assumed displacement. The force-displacement relationship shall be determined by a nonlinear analysis. The force-displacement analysis shall include the calculation of the displacement at which strength degradation begins. EXCEPTION: The initial effective moment of inertia of beams and columns in shear wall or infilled frame buildings may be estimated using Table 71-B. The ratio of effective moment of inertia used for the beams and for the columns shall be verified by Formulas (71-1), (71-2) and (71-3). The estimates shall be revised if the ratio used exceeds the ratio calculated by more than twenty percent (20%). [image omitted; see the official code] (71-1) WHERE: [image omitted; see the official code] (71-2) and [image omitted; see the official code] (71-3) 2. Infills. The effective stiffness of an infill shall be determined from a nonlinear analysis of the infill and the confining frame. The effect of the infill on the stiffness of the system shall be determined by differencing the force-displacement relationship of the frame-infill system from the frame-only system. 3. Model of infill. The mathematical model of an infilled frame structure shall include the stiffness effects of the infill as a pair of diagonals in the bays of the frame. The diagonals shall be considered as having concrete properties and only axial loads. Their lines of action shall intersect the beam-column joints. The secant stiffness of the force-displacement relationship, calculated as prescribed in Subsection 18.71.060.D.2, shall be used to determine the effective area of the diagonals. The effective stiffness of the frame shall be determined as specified in Subsection 18.71.060.D.1. Other procedures that provide the same effective stiffness for the combination of infill and frame may be used when approved by the Building Official. 4. Effective stiffness of elements and systems. The effective stiffness shall be determined by an iterative method. The mathematical model using assumed effective stiffness shall be used to calculate dynamic displacements. The effective stiffness of all concrete and masonry elements shall be modified to represent the secant stiffness obtained from the nonlinear force displacement analysis of the element or system at the calculated displacement. A reanalysis of the mathematical model shall be made using the adjusted effective stiffness of existing and supplemental elements and systems until closure of the iterative process is obtained. A difference of ten percent (10%) from the effective stiffness used and that recalculated may be assumed to be closure of the iterative process. E. Description of analysis procedures. 1. Response spectrum analysis. Response spectrum analysis is an elastic dynamic analysis of a structure utilizing the peak dynamic response of all modes having a significant contribution to total structural response. Peak modal responses are calculated using the ordinates of the appropriate response spectrum curve that correspond to the modal periods. Maximum modal contributions are combined in a statistical manner to obtain an approximate total structural response. 2. Number of modes. The requirement of Subsection 18.71.060.E.1 may be satisfied by demonstrating that for the modes considered, at least ninety percent (90%) of the participating mass of the structure is included in the calculation of response for each principal horizontal direction. 3. Combining modes. The peak displacements for each mode shall be combined by recognized methods. Modal interaction effects of three-dimensional models shall be considered when combining modal maxima. 4. Torsion. The three-dimensional analysis shall be considered as including all torsional effects including accidental torsional effects. F. Material characteristics. The stress-strain relationship of concrete, masonry and reinforcement shall be determined by testing or from published data. The procedure for testing and determination of stress-strain values shall be as prescribed in one of the following: 1. Concrete. The compressive strength of existing concrete shall be determined by tests on cores sampled from the structure or may be taken from information given on the construction documents and confirmed by limited testing. A default value of horizontal shear stress may be used in Subsection 18.71.080.E.1 without testing of the compressive strength of the existing concrete. a. The cutting of cores shall not significantly reduce the strength of the existing structure. Cores shall not be taken in columns. Existing reinforcement shall not be cut. b. If the construction documents do not specify a minimum compressive strength of the classes of concrete, five (5) cores per story, with a minimum of ten (10) cores, shall be obtained for testing. Exception: If the coefficient of variation of the compressive strength does not exceed fifteen percent (15%), the number of cores per story may be reduced to two (2) and the minimum number of tests reduced to five (5). c. When the construction documents specify a minimum compressive strength, two (2) cores per story, per class of concrete, shall be taken in the areas where that concrete was to be placed. A minimum of five (5) cores shall be obtained for testing. If a higher strength of concrete was specified for columns than the remainder of the concrete, cores taken in the beams for verification of the specified strength of the beams shall be substituted for tests in the columns. The strength specified for columns may be used in the analyses if the specified compressive strength in the beams is verified. d. The sampling for the concrete strength tests shall be distributed uniformly in each story. If the building has shear walls, a minimum of fifty percent (50%) of the cores shall be taken from the shear walls. Not more than twenty-five percent (25%) of the required cores shall be taken in floor and roof slabs. The remainder of cores may be taken from the center of beams at mid-span. In concrete frame buildings, seventy-five percent (75%) of the cores shall be taken from the beams. e. The mean value of the compressive stresses obtained from the core testing for each class of concrete shall be used in the analyses. Values of peak strain that is associated with peak compressive stress may be taken from published data for the nonlinear analyses of reinforced concrete elements. 2. Solid grouted reinforced masonry. The compressive strength of solid grouted concrete block or brick masonry may be taken as two thousand (2,000) psi. The strain associated with peak stress may be taken as 0.0025. 3. Partially grouted masonry. A minimum of five (5) units shall be removed from the walls and tested in conformance with ASTM C90-14 Specification for Load Bearing Concrete Masonry Units. Compressive strength of the masonry may be determined in accordance with Chapter 21 of the California Building Code adopted in Chapter 18.40, assuming Type S mortar. The strain associated with peak stress may be taken as 0.0025. 4. Unreinforced masonry. a. The stress-strain relationship of existing unreinforced masonry shall be determined by in-place cyclic testing. The test procedure shall conform to Section 18.71.100. b. One (1) stress-strain test per story and a minimum of five (5) tests shall be made in the unreinforced masonry infills. The location of the tests shall be uniformly distributed throughout the building. c. The average values of the stress-strain values obtained from testing shall be used in the nonlinear analyses of frame-infill assemblies or in the calculation of the effective diagonal brace that is used in the simplified analysis procedure of Section 18.71.080. 5. Reinforcement. The yield stress of each type of new or existing reinforcement shall be taken from Table 71-C unless the reinforcement is sampled and tested for yield stress. The axial reinforcement in columns of post-1933 buildings shall be assumed to be hard grade unless noted otherwise on the construction documents. 6. Combination of concrete and masonry materials. Combinations of masonry and concrete infills shall be assumed to have equal strain. The secant moduli at peak stress of the masonry and concrete shall be used to determine the effective transformed area of the composite material. G. Story drift limitation. 1. Definition. Story drift is the displacement of one level relative to the level above or below calculated by the response spectrum analysis using the appropriate effective stiffness. 2. Limitation. The story drift is limited to that displacement that causes any of the following effects: a. Compressive strain of 0.003 in the frame confining infill or in a shear wall. b. Compressive strain of 0.004 in a reinforced concrete column unless the engineer can show by published experimental research that the existing confinement reinforcement justifies higher values of strain. c. Peak strain in masonry infills as determined by experimental data or by physical testing as prescribed in Section 18.71.100. d. Displacement that was calculated by the nonlinear analysis as when strength degradation of any element began. EXCEPTION: This subsection may be taken as the displacement that causes a strength degradation in that line of resistance equal to ten percent (10%) of the sum of the strength of the elements in that line of resistance. e. A story drift of 0.015 using the dynamic analysis procedure or the forces specified in Section 18.71.070. This limitation shall not supersede the limitations of Subsections 18.71.060.G.2.a through 18.71.060.G.2.d. H. Compressive strain determination. 1. General. The compressive strain in columns, shear walls and infills may be determined by the nonlinear analysis or a procedure that assumes plane sections remain plane. 2. Axial and flexural loading. The compressive strain shall be determined for combined flexure and axial loading. The flexural moments shall be taken from the response spectrum model for frame or shear wall buildings, and from the substructure model for infill frames. The axial loads shall have the following combination of effects, where L is unreduced live load: U = 1.0D + 0.3L + 1.0E(71-4) U = 0.9D - 1.0E(71-5) I. Shear strength limitation. The required in-plane shear strength of all columns, piers and shear walls shall be the shear associated with the moments induced at the ends of columns or piers and at the base of shear walls by the story displacements. No strength reduction factors shall be used in the determination of strength.
(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022; ORD-19-0031 § 1(Exh. A), 2019; ORD-16-0026 § 1(Exh. A), 2016)
Ask a question about Long Beach law
Corpus searches the Long Beach sections it holds and shows the ones that match, with their citations. Free, no sign-in.