52-36. - Policy.
A. No water service connection to any premises shall be installed or maintained by the City unless the water supply is protected as required by State laws and regulations and this article. Service of water to any premises may be discontinued by the City if a backflow prevention device required by this article is not installed, tested, and maintained; or if it is found that a backflow prevention device has been removed or by-passed; or if an unprotected cross-connection exists on the premises. Service will not be restored until such conditions or defects are corrected.
B. The customer's system should be open for inspection at all reasonable times to authorized representatives of the City to determine whether cross-connections or other structural or sanitary hazards, including violations of these regulations, exist. When such a condition becomes known, the Director of the Public Works and Utilities Department may deny or immediately discontinue service to the premises by providing for a physical break in the service line until the customer has corrected the condition(s) in conformance with the State and City statutes relating to plumbing and water supplies and the regulations adopted pursuant thereto.
C. An approved backflow prevention device shall also be installed on each service line to a customer's water system in all cases before the first branch line leading off the service line wherever the following conditions exist:
1. In the case of premises having an auxiliary water supply which is not or may not be of safe bacteriological or chemical quality and which is not acceptable as an additional source by the Director of the Public Works and Utilities Department, the public water system shall be protected against backflow from the premises by installing a backflow prevention device in the service line appropriate to the degree of hazard.
2. In the case of premises on which any industrial fluids or any other objectionable substance is handled in such a fashion as to create an actual or potential hazard to the public water system, the public system shall be protected against backflow from the premises by installing a backflow prevention device in the service line appropriate to the degree of hazard. This shall include the handling of processed waters and waters originating from the utility system which have been subject to deterioration in quality.
3. In the case of premises having a) internal cross-connections that cannot be permanently corrected and controlled, or b) intricate plumbing and piping arrangements or where entry to all portions of the premises is not readily accessible for inspection purposes, making it impracticable or impossible to ascertain whether or not dangerous cross-connections exist, the public water system shall be protected against backflow from the premises by installing a backflow prevention device in the service line.
D. The type of protective device required shall depend upon the degree of hazard which exists as follows:
1. In the case of any premises where there is an auxiliary water supply and it is not subject to any of the following rules, the public water system shall be protected by an approved air-gap separation or an approved reduced pressure principle backflow prevention device.
2. In the case of any premises where there is water or substance that would be objectionable but not hazardous to health, if introduced into the public water system, the public water system shall be protected by an approved double check valve assembly.
3. In the case of any premises where there is any material dangerous to health which is handled in such a fashion as to create an actual or potential hazard to the public water system, the public water system shall be protected by an approved air-gap separation or an approved reduced pressure principle backflow prevention device. Examples of premises where these conditions will exist include chemical manufacturing plants, hospitals, mortuaries, plating plants, sewage treatment plants and sewage pumping stations.
4. In the case of any premises where there are "uncontrolled" cross-connections, either actual or potential, the public water system shall be protected by an approved air-gap separation or an approved reduced pressure principle backflow prevention device at the service connection.
5. In the case of any premises where, because of security requirements or other prohibitions or restrictions it is impossible or impracticable to make a complete in-plant cross-connection survey, the public water system shall be protected against backflow from the premises by the installation of a backflow prevention device in the service line. In this case, maximum protection will be required; that is, an approved air-gap separation or an approved reduced pressure principle backflow prevention device shall be installed on each service to the premises.
6. In the case of water tankers and spray tanks, an air-gap separation or an approved reduced pressure principle backflow prevention device is required.
E. Backflow prevention assemblies shall have at least the same cross-sectional area as the water service and/or meter. If the water supply cannot be temporarily interrupted for the testing of assemblies, in those instances where a continuous water supply is necessary, two (2) sets of backflow prevention assemblies shall be installed in parallel.
F. Any backflow prevention device required herein shall be of a model and size approved by the Director of the Public Works and Utilities Department. The term "approved backflow prevention device" shall mean a device that has been manufactured in full conformance with the standards established by the American Water Works Association (AWWA) entitled "AWWA C506-78 Standards for Reduced Pressure Principle and Double Check Valve Backflow Prevention Devices"; and have met completely the laboratory and field performance specifications of the Foundation for Cross-Connection Control and Hydraulic Research (FCCC & HR) of the University of Southern California; and has a local parts and service center. Backflow prevention assemblies connected to fire lines must also carry UL-FM approval.
The AWWA and FCCC & HR standard and specifications have been adopted by the Director of the Public Works and Utilities Department. Final approval shall be evidenced by a certificate of approval issued by an approved testing laboratory certifying full compliance with the AWWA standards and FCCC & HR specifications. The following testing laboratory has been qualified by the Director of the Public Works and Utilities Department to test and certify backflow prevention assemblies:
Foundation for Cross-Connection Control and Hydraulic Research
University of Southern California
University Park
Los Angeles, California 90007
Backflow prevention assemblies which may be subjected to back-pressure or back-siphonage that have been fully tested, and have been granted a certificate of approval by FCCC & HR may be listed on the current list of "Approved Backflow Prevention Assemblies," which will be made available upon written request to the Department.
G. It shall be the duty of the customer/user at any premises where backflow prevention devices are installed to have certified inspections and operational tests and repairs made at least once per year. In those instances where the Director of the Public Works and Utilities Department deems the hazard to be great enough, he/she may require certified inspections at more frequent intervals. These inspections, tests and repairs shall be at the expense of the water user and shall be performed by the device manufacturer's representative, or by a certified tester approved by the Director of the Public Works and Utilities Department.
H. Assemblies shall be specified and located on the construction plans for all new buildings, additions with new services, and changes of use of existing buildings. Approval shall be obtained prior to issuance of the building permit. This section does not apply to building permits applied for prior to the effective date of this article [November 1, 1990].
I. All presently installed backflow prevention devices which do not meet the requirements of this section but were approved devices for the purposes described herein at the time of installation and which have been properly maintained shall, except for the inspection and maintenance requirements, be excluded from the requirements of these rules so long as the Director of the Public Works and Utilities Department is assured that they will satisfactorily protect the utility system. Whenever the existing device is moved from the present location or requires more than minimum maintenance or when the Director of the Public Works and Utilities Department finds that the maintenance constitutes a hazard to health, the unit shall be replaced by a backflow prevention device meeting the requirements of this section.
J. The Director of the Public Works and Utilities Department or his/her designated representative shall maintain a list of approved backflow prevention assemblies, by type and manufacturer, and a list of certified, approved and recognized individuals to test or perform servicing of those assemblies. The list shall be furnished to any customer required to install or maintain a backflow prevention assembly.
(Ord. No. 2149, § 1.B, 9-13-90; Ord. No. 3060, § 2, 11-18-99; Ord. No. 4365, § 33, 6-14-12; Ord. No. 4802, § 2(Exh., § 35), 4-26-18)