Proposed remedy provisions (remedies for interruption or blockage to the microwave loop infrastructure), as outlined herein, shall be agreed upon and accepted by the owner/applicant/designee and the city within the application phase and shall be adhered to during and after completion of construction. The owner/applicant/designee may opt for either of the following remedies:
(1) At no cost to the city, the owner/applicant/designee shall be responsible for:
a. The installation and operation of communications antennas, microwave, and transmission lines, as required, and the roof top space for said equipment. The roof top space shall have an area of no less than ten feet by ten feet (10' x 10'). All communications antennae and transmission line requirements shall be determined by the city's RCL, as per industry standards, and shall meet all federal, state, and local requirements. All proposed roof top space shall be reviewed by the city's RCL to ensure that the space is adequate for the restoration of the microwave system.
b. Providing no less than 200 square feet of enclosed air-conditioned space adjacent to the antennae installations for the city to place, install, and operate communications radio equipment. This room shall have at least 200 amperes electrical capacity. Electricity for said enclosed area will be on a separate meter and billed to the city. The building owner or designee shall be responsible for maintaining the air conditioning, space, and providing the city with access to all meters. The building owner or designee shall provide emergency backup power as specified by the city's RCL. The building owner or designee shall be responsible for meeting manufacturer's environmental requirements for all equipment located in said enclosed space (e.g. temperature, humidity, etc.). If the environmental requirements are not met and damage is caused to the equipment located within the space, the building owner or designee may be liable for damages caused to the equipment.
c. Reimbursing the city for any and all transmission equipment, installation, licensing, permitting, etc. (e.g. radios, antennae, cable trays, generators, UPS, etc.) needed for the city's microwave signals to continue to its original destination at the original signal strength (i.e. with no loss in signal or degradation), as determined necessary by the city. The equipment may be passive or active microwave systems (limited to the restoration of the microwave levels). The city reserves the right to replace or upgrade all equipment as required at the city's expense and the building owner or designee shall provide access to city personnel for such replacement or upgrade.
d. Providing an alternate signal routing either by using a local provider T1 or fiber-type service, during the construction and prior to interruption of microwave signals, to maintain or restore service to the city's communication sites. Alternative signal routing proposals must be reviewed and authorized by the city's RCL prior to implementation.
(2) At no cost to the city, the owner/applicant/designee shall be responsible for providing alternative solutions by either reducing the obstructing height, relocating the obstruction elsewhere, or other solutions acceptable to the city's RCL.