Cicero Municipal Code § 22-206 Systems operated above atmospheric pressure; table.
Sec. 22-206. - Systems operated above atmospheric pressure; table.
Refrigerating systems normally operated above atmospheric pressure shall be equipped with safety devices according to the following table:
Nonflammable and Nonirritant
Class 1 | Class 2 | Irritant or Flammable Refrigerants
System Class | System Class | System Class
Safety device location and venting | A | B | C | D | E | A | B | C | D | E | A | B | C | D | E
Pressure-limiting device | X | X | X | X | X | X | X | X | X | X | X | X
Pressure vessel relief device | X | X | X | X | X | X | X | X | X | X | X | X | X | X | X
Vent to atmosphere | X | X | X | X | X | X | X | X | X | X | X
Compressor or other pressure-imposing element relief device | X | X | X | X | X | X | X | X | X
Emergency relief valve | X | X | X | X | X
Discharge checkvalve | X | X | X
Quick closing suction valve | X | X | X
_____
(Ord. of 7-19-1948, § 59; Code 1958, § 28-27)