Sec. 22-208. - Shell-type equipment; table for inlet size of relief devices.

(a) Shell-type apparatus for refrigerating systems such as condensers, liquid receivers, evaporators, liquid separators and absorbers, shall be equipped with an approved pressure-relief device set at a pressure not to exceed the pressure for which the vessel is designed. The inlet size of these relief devices shall be based on the refrigerating capacity for which the pressure vessel is designed and shall be sized in accordance with the following table: Refrigerating Capacity (tons) | Relief Device Pipe Size (inches) Up to 15 | ⅜ 16 to 30 | ½ 31 to 60 | ¾ 61 to 100 | 1 101 to 175 | 1¼ 176 to 250 | 1½ 251 to 450 | 2 451 to 900 | 2 (b) The discharge connection from these relief devices shall be equal to or greater than the inlet connection to the relief device. (c) A fusible plug shall not be permitted as a relief device.

(Ord. of 7-19-1948, § 61; Code 1958, § 28-29)