Sec. 22-209. - Pressure-relief device required on compressors.
(a) Compressors on class A, B and C refrigerating systems, except those containing 50 pounds or less of nonirritant and nonflammable refrigerant, shall be equipped with a pressure-relief device located between the pressure-imposing element and the stop valve on the discharge side. Such valves shall be set at not more than 90 percent of the test pressure specified for the refrigerant used. Where a flammable or irritant refrigerant or a class 2 nonflammable or nonirritant refrigerant is used, this device shall be vented into the low pressure side of the system. Where a class 1 nonflammable and nonirritant refrigerant is used, this device may discharge to the atmosphere but shall be piped to discharge toward the ceiling, not less than seven feet above the floor. Systems containing 100 pounds or more of class 1 nonflammable and nonirritant refrigerant shall be vented to the outside atmosphere or to the suction side. In systems where the pressure-imposing element is a compressor, the inlet pipe size of the relief devices shall be based on the gross displacement of the compressor and shall conform to the following table: Cubic Feet Per Minute | Relief Device Size (inches) Up to 25 | ⅜ 26 to 100 | ½ 101 to 200 | ¾ 201 to 350 | 1 351 to 580 | 1¼ 581 to 850 | 1½ 851 to 1,500 | 2 (b) In systems where the pressure-imposing element is other than a compressor, the department for the inspection of steam boilers, unfired pressure vessels, and cooling plants shall determine the size of the relief devices to be used. (c) The discharge connection from these relief devices shall be equal to or greater than the inlet connection to the relief device.
(Ord. of 7-19-1948, § 62; Code 1958, § 28-30)
Ask a question about Cicero law
Corpus searches the Cicero sections it holds and shows the ones that match, with their citations. Free, no sign-in.