Sec. 22-212. - Hand-operated relief valve.

(a) A hand-operated relief valve or other approved means for transferring refrigerant from a building where an emergency condition may exist must be provided for refrigerating systems in accordance with the table of safety devices in section 22-206. (b) Where a hand-operated relief valve is used, it shall be of two-inch diameter for class B systems and three-inch diameter for class A systems. Such valves shall be connected to the low pressure side of the system and arranged or located so that they may be operated outside of the entrance to the machinery room. (c) These valves shall be vented to the atmosphere as further provided. (d) Valves shall be identified with a permanent tag containing instructions for operation.

(Ord. of 7-19-1948, § 65; Code 1958, § 28-33)