ALTERNATE WATER SOURCES FOR NON-POTABLE APPLICATIONS.
Austin City Code § 15-1-19
in effect§ 15-1-19 - ALTERNATE WATER SOURCES FOR NON-POTABLE APPLICATIONS.
(A) Registration required. Except as provided under Subsection (B), an alternate water system must be registered with Austin Water by a customer or their authorized representative. Registration shall be on a form approved by the director. Registration includes:
(1) site address for the alternate water system;
(2) storage capacity for the alternate water system;
(3) type of alternate water system; and
(4) intended use for the alternate water.
(B) A residential non-potable rainwater catchment or non-potable condensate collection system that is 500 gallons or less and used for outdoor applications is not required to be registered.
(C) Inspection and testing.
(1) Alternate water source systems shall be inspected and tested:
(a) for cross-connections in accordance with this chapter; and
(b) to determine compliance with provisions in the Plumbing Code related to potable water piping.
(D) Cross-connection Inspection and Testing. Except as provided under subdivisions (1) and (2), initial and subsequent inspections and tests shall be performed on both the potable and alternate water source systems. The potable and alternate water source system shall be isolated from each other and independently inspected and tested to ensure there is no cross-connection in accordance with Section 15-1-19(F). The following types of systems are not required to have cross-connection testing:
(1) gravity type exterior non-potable condensate collection systems; and
(2) non-potable condensate collection systems with less than a 500-gallon capacity and used for outdoor applications.
(E) Visual system inspection. Before commencing the cross-connection testing, a dual system inspection shall be conducted by a licensed professional, registered with the utility. A dual system inspection requires checking:
(1) meter locations of the alternate water source and potable water lines to verify that no modifications were made and that no cross-connections are visible;
(2) pumps and equipment, equipment room signs, and exposed piping in equipment rooms;
(3) valves to ensure that the valve lock seals are still in place and intact; and
(4) valve control door signs to verify that no signs have been removed.
(F) Cross-connection Test. To determine whether a cross-connection has occurred, a licensed professional, registered with the utility, must follow the procedures described in this section. These procedures shall be followed for all non-potable alternate water sources requiring cross-connection tests. The results of the test shall be submitted on a form approved by the director.
(1) The potable water system shall be activated and pressurized; and the alternate water source system shall be shut down, depressurized, and drained.
(2) The potable water system shall remain pressurized for a minimum period specified by the utility while the alternate water source is empty. The minimum period the alternate water source system is to remain depressurized shall be determined on a case-by-case basis, considering the size and complexity of the potable and the alternate water source distribution systems, but in no case shall be less than one hour.
(3) The drain on the alternate water source system shall be checked for flow during the test, and fixtures, and potable and alternate water sources shall be tested and inspected for flow. Flow from an alternate source system outlet indicates a cross-connection. No flow from a potable water outlet shall indicate that it is connected to the alternate water source system.
(4) The potable water system shall then be depressurized and drained.
(5) The alternate water source system shall then be activated and pressurized.
(6) The alternate water source system shall remain pressurized for a minimum period specified by the utility while the potable water system is empty. The minimum period the potable water system is to remain depressurized shall be determined on a case-by-case basis, but in no case shall that period be less than one hour.
(7) Fixtures, potable, and alternate water source shall be tested and inspected for flow. Flow from a potable water system outlet indicates a cross-connection. No flow from an alternate water source outlet will indicate that it is connected to the potable water system.
(8) The drain on the potable water system shall be checked for flow during and at the end of the test.
(9) If there is no flow detected in the fixtures which would indicate a cross-connection, the potable water system shall be re-pressurized.
(G) Discovery of Cross-Connection. If a cross-connection is discovered, the following procedure, in the presence of the utility employee, shall be activated immediately:
(1) the alternate water source piping to the building shall be shut down at the meter or source, and the alternate water source system shall be drained;
(2) potable water piping to the building shall be shut down at the meter;
(3) the cross-connection shall be uncovered and disconnected;
(4) the building shall be retested in accordance with Section 15-1-19(F);
(5) the potable water system shall be chlorinated with 50 parts-per-million (ppm) chlorine for 24 hours; and
(6) the potable water system shall be flushed after 24 hours, and a standard bacteriological test shall be performed. If test results are acceptable, the potable water system shall be permitted to be recharged.
(H) Alternate Cross-Connection Test Methods. Alternate cross-connection test procedures may be authorized by the utility. For an alternate method to be approved, an Austin Water Alternate Method of Compliance form shall be submitted before construction of an alternate water system begins.
(I) License Required. An alternate water system inspection and cross-connection test shall be performed by:
(1) a plumbing inspector licensed by the Texas State Board of Plumbing Examiners;
(2) a journeyman or master plumber licensed with the Texas State Board of Plumbing Examiners with a water supply protection specialist endorsement; or
(3) a customer service inspector licensed by the commission.
(J) Reoccurring Inspection and Testing. Reoccurring inspections and cross-connection testing of the alternate water source system, consistent with Sections 15-1-19(C), (D), (E), and (F), or approved alternate test, are required unless site conditions do not require it. Inspections and testing for black water sourced alternate water systems shall occur annually. Inspections and cross-connection testing for all other alternate water systems for multi-family, industrial, institutional, or commercial sites shall occur once every four years. Cross-connection testing is required at any time the potable water system or alternate water system is altered or when required by the Utility. Test results shall be submitted on a form approved by the director.
(K) Connections to Potable Water. Alternate water source systems shall be permitted to have potable water makeup with the following requirements:
(1) Gray water systems shall have no direct connection to a potable water supply. Potable water is permitted to be used as makeup water for a non-pressurized storage tank provided the connection is protected by an air gap in accordance with this chapter. On-site treated non-potable water, and reclaimed water may be used as makeup water.
(2) Reclaimed water systems are prohibited from connecting to a potable water supply system. Potable water is permitted to be used as makeup water for a reclaimed water storage tank if the water supply inlet is protected by an air gap. An alternate water source may be used if adequate backflow protection is installed.
(3) Makeup water to other alternate systems requires an air gap or reduced pressure zone backflow preventer.
(L) Initial Inspection and Cross-Connection Test for Reclaimed Water Sites. Before a building is occupied or the system is activated, an inspection, and cross-connection test that complies with Sections 15-1-19(C)—(F), or an approved alternate test, is required. Final approval cannot be granted until the test is deemed successful by the Utility. An annual inspection and cross-connection test shall occur.
(M) Initial Inspection and Cross-Connection Test for On-site Water Reuse System Sites. Before a building is occupied or the system is activated, an inspection and cross-connection test that complies with Sections 15-1-19(C)—(F), or an approved alternate, is required. Final approval cannot be granted until the test is deemed successful by the Utility. An inspection and cross-connection test shall occur once every four years for multi-family, industrial, institutional, or commercial sites.
(N) Initial Inspection and Cross-Connection Test for Other Alternate Water Systems. Before a building is occupied or the system is activated, an inspection and cross-connection test that complies with Sections 15-1-19(C)—(F), or an approved alternate, is required. Final approval cannot be granted until the test is deemed successful by the Utility. An inspection and cross-connection test shall occur once every four years for multi-family, industrial, institutional, or commercial sites.
(O) Initial Inspection and Cross-Connection Test for Non-Potable Rainwater Catchment Sites. Except as provided in subdivisions (1) and (2), before a building is occupied or the system is activated, a cross-connection test that complies with Sections 15-1-19(C)—(F), or an approved alternate test, is required. Final approval cannot be granted until the test is deemed successful by the Utility. An inspection and cross-connection test shall occur once every four years. Test results shall be submitted on a form approved by the director.
(1) The following type of rainwater catchment systems are not required to have cross-connection testing: A non-potable rainwater catchment system of 500 gallons or less and used for outdoor applications; or
(2) Gravity type exterior non-potable rainwater catchment systems.
(P) Hose Bibs. Hose bibs shall not be allowed on reclaimed water piping systems. Access to reclaimed water shall be through a quick-disconnect device that differs from those installed on the potable water system. Such outlets supplying reclaimed water shall be marked with the words: "CAUTION: NON-POTABLE RECLAIMED WATER, DO NOT DRINK" and the symbol below. Hose bibs on other alternate water systems shall be allowed and shall be marked with the words: "CAUTION: NON-POTABLE WATER, DO NOT DRINK" and the symbol below.
[image omitted; see the official code]
(Q) Changes to Potable Water or Alternate Water Systems. On sites utilizing alternate water, no changes or connections to either the alternate water system or the potable water system shall be made without first obtaining approval from the director and any other authority having jurisdiction.
Source: Ord. No. 20250410-002, Pt. 1, 4-21-25.