§ 15-1-14 - CROSS-CONNECTION CONTROL—ASSEMBLIES, DEVICES AND METHODS.
(A) The following types of backflow prevention devices, assemblies, and methods can be used for cross-connection:
(1) Air Gap: If used to provide backflow protection, the minimum air gap shall be designed in accordance with Table 15-1-14-B.
(2) Atmospheric Vacuum Breaker: A body, a checking member, and an atmospheric port.
(3) Hose Connection Backflow Preventer: Two independent check valves with an independent atmospheric vent in between and a means of field testing and draining.
(4) Double Check Valve Backflow Prevention Assembly: Two independently acting internally loaded check valves, four properly located test ports, and two isolation valves.
(5) Pressure Vacuum Breaker Backflow Prevention Assembly (PVB): A loaded air inlet valve, an internally loaded check valve, two properly located test ports, and two isolation valves. This device shall be permitted to be installed indoors where provisions for spillage are provided.
(6) Spill-Resistant Pressure Vacuum Breaker: One check valve force loaded closed and an air inlet vent valve force loaded open to atmosphere, positioned downstream of the check valve and located between and including two tightly closing shutoff valves and test ports.
(7) Reduced Pressure Principle Backflow Prevention Assembly: Two independently acting internally loaded check valves, a differential pressure relief valve, four properly located test ports, and two isolation valves.
(8) Double Check Detector Fire Protection Backflow Prevention Assembly: A double check valve assembly with a parallel detector assembly consisting of a water meter and a double check valve backflow prevention assembly.
(9) Double Check Detector Fire Protection Backflow Prevention Assembly Type II (DCDA II): A double check valve assembly with a parallel bypass consisting of two shutoff valves, two test ports, a meter, and a single check valve. This bypass assembly connects upstream and downstream of the main second check valve.
(10) Reduced Pressure Detector Fire Protection Backflow Prevention Assembly (RP): A reduced pressure principle backflow prevention assembly with a parallel detector assembly consisting of a water meter and a reduced pressure principle backflow prevention assembly.
(11) Reduced Pressure Detector Fire Protection Backflow Prevention Assembly Type II: Two shutoff valves, two test ports, a meter, and a single check valve. This bypass assembly connects upstream and downstream of the main second check valve and utilizes the reduced pressure zone and relief valve of the main assembly.
(12) Dual Check Backflow Preventer: Two independently acting check valves, force loaded to a normally closed position.
(13) Laboratory Faucet Backflow Preventer: Can be used if it complies with ASSE 1035.
(14) Backflow Preventer with Intermediate Atmospheric Vent: Two independently acting check valves, force loaded to a normally closed position and an intermediate chamber with a means for automatically venting to the atmosphere, force loaded to a normally open position.
(B) The following requirements apply to backflow prevention devices, assemblies and methods used in cross-connection:
(1) Where more than one backflow prevention valve is installed on a single premise, and the valves are installed in one location, each separate valve shall be permanently identified in a manner satisfactory to the utility.
(2) Backflow prevention devices, assemblies, and methods shall be constructed with adequate access and clearance, in accordance with the manufacturer's instructions, and with not less than 12 inches (305 mm) between the lowest portion of the assembly and the grade, floor, or platform. Elevated installations of backflow prevention devices, assemblies, and methods that exceed five feet (1,524 mm) above the floor or grade shall be required to provide a platform capable of supporting a technician.
(3) Direct connection between potable water piping and sewer-connected wastes is prohibited. If potable water is discharged to the drainage system, it can only be discharged through an approved air gap of two pipe diameters of the supply inlet, but in no case shall the gap be less than one inch (25.4 mm). Connection shall be permitted to be made to the inlet side of a trap provided that an approved vacuum breaker is installed not less than six inches (152 mm) or the distance according to the backflow prevention device's listing, above the flood-level rim of such trapped fixture, so that at no time will such device be subjected to backpressure.
(4) Backflow preventers for hot water exceeding 110°F (43°C) shall be designed to operate at temperatures above 110°F (43°C) without rendering a portion of the assembly inoperative.
(5) Fixtures, appliances, or appurtenances with integral backflow preventer or integral air gaps manufactured as a unit shall be installed in accordance with their listing requirements and the manufacturer's installation instructions.
(6) Backflow assemblies and devices shall be protected from freezing with an outdoor enclosure that complies with ASSE 1060 or by a method acceptable to the utility.
(7) Drain lines serving backflow devices or assemblies shall be sized in accordance with the discharge rates of the manufacturer's flow charts for such devices or assemblies.
(8) Backflow prevention devices with atmospheric vents or ports shall not be installed in pits, underground, or submerged locations. A backflow preventer shall not be located in an area containing fumes that are toxic, poisonous, or corrosive.
(9) Except for potable water supplied to carbonators, a separate backflow prevention assembly or device shall be installed on a high hazard appurtenance or fixture in high hazard situations when water or product is intended for contact with humans either directly (consumption, bathing, medical uses, dental chairs, pharmaceuticals, etc.) or indirectly (sterilization, autoclaves, washing dishes or bottles, canning, etc.).
(10) Potable water supplied to carbonators shall be protected with a listed reduced pressure principle backflow preventer that is approved by the utility for that specific use. A single reduced pressure principle backflow prevention assembly may be installed for multiple carbonators that are located in the same immediate physical area if all water piping from the backflow preventer to the carbonator is exposed. Piping downstream of backflow protection for carbonators cannot be affected by carbon dioxide gas.
(11) If no human contact is intended for a water line downstream of a backflow prevention assembly or backflow prevention device, then a single backflow prevention assembly or backflow prevention device may be installed for multiple high hazard appurtenances or fixtures. Each water line downstream of the backflow protection must be labeled consistent with Section 15-1-13(A)(3).
(12) In low hazard situations that service multiple low hazards of the same type and are located in the same immediate physical area, a single backflow prevention assembly or device may be installed if all piping downstream of the backflow preventer is exposed. Each water line downstream of the backflow protection must be labeled consistent with the requirements for non-potable water piping.
(C) Additional Requirements for backflow prevention: In addition to the requirements of Subsection (B), the following will apply depending on the type of device being installed, as outlined below:
(1) Atmospheric Vacuum Breakers. Water closet and urinal flushometer valves shall be protected against backflow by an atmospheric vacuum breaker installed on the discharge side of the flushometer valve with the critical level not less than six inches (152 mm), or the distance according to its listing, above the overflow rim of a water closet bowl or the highest part of a urinal.
(2) Ballcock. Water closet and urinal tanks shall be equipped with a ballcock installed with the critical level not less than one inch (24.4 mm) above the full opening of the overflow pipe. In cases where the ballcock has no hush tube, the bottom of the water supply inlet shall be installed one inch (24.4 mm) above the full opening of the overflow pipe.
(3) Water Closet Flushometer Tanks. Water closet flushometer tanks shall be protected against backflow by an approved backflow prevention assembly, device, or method.
(4) Heat Exchangers. Heat exchangers used for heat transfer, heat recovery, or solar heating shall protect the potable water system from being contaminated by the heat-transfer medium. Single wall heat exchangers used in indirect-fired water heaters shall meet the requirements for single-wall heat exchangers in Section 505.4.1 of the Plumbing Code.
(5) Water Supply Inlets. Water supply inlets to tanks, vats, sumps, and other receptors shall be protected by an air gap, a listed vacuum breaker installed on the discharge side of the last valve with the critical level not less than six inches (152mm) above all downstream piping and the flood level rim of the receptor, or a backflow prevention assembly suitable for the degree of hazard.
(6) Lawn Sprinklers and Irrigation Systems. Potable water to lawn sprinklers and irrigation systems that lack pumps or connections for pumping equipment and lack chemical injection or the provisions for chemical injection must be protected from backflow using one of the following:
(a) pressure vacuum breaker backflow prevention assembly;
(b) spill-resistant pressure vacuum breaker;
(c) reduced pressure principle backflow prevention assembly; or
(d) double check valve assembly.
(7) Systems with Pumps. If sprinkler and irrigation systems have pumps, or connections for pumps, auxiliary air tanks, or are otherwise capable of creating backpressure, the potable water supply shall be protected by a reduced pressure principle backflow prevention assembly or double check valve located upstream of the source of backpressure.
(8) Systems with Backflow Devices. The backflow device installed downstream from a potable water supply pump or a potable water supply pump connection must be a:
(a) pressure vacuum breaker backflow prevention assembly;
(b) spill-resistant pressure vacuum breaker;
(c) reduced pressure principle backflow prevention assembly; or
(d) double check valve assembly.
(9) Systems with chemical injectors. The potable water supply shall be protected by a reduced pressure principle backflow prevention assembly in a system with a chemical injector or provisions for chemical injection.
(10) Outlets with Hose Attachments. Potable water outlets with hose attachments, other than water heater drains, boiler drains, and clothes washer connections, shall be protected by a nonremovable hose bib type backflow preventer, a nonremovable hose bib vacuum breaker, or an atmospheric vacuum breaker installed not less than six inches (152 mm) above the highest point of usage located on the discharge side of the last valve. The customer shall install protective measures to mitigate outside outlets from freezing.
(11) Water Cooled Equipment. Water cooled compressors, degreasers, or other equipment shall be protected with appropriate backflow prevention based on the type of hazard present.
(12) Aspirators. Water inlets to water-supplied aspirators shall be equipped with a vacuum breaker installed in accordance with its listing requirements and this chapter. The discharge shall drain through an air gap. The air gap shall be located above the flood-level rim of the fixture if a fixture tailpiece is to be used to receive the discharge of an aspirator.
(13) Steam or Hot Water Boilers. Potable water connections to residential steam or hot water boilers shall be protected from backflow by a double check valve assembly, backflow preventer with intermediate atmospheric vent and pressure reducing valve, or reduced pressure principle assembly in accordance with Table 15-1-14-A. A reduced pressure principle assembly shall be provided if chemicals are to be introduced into the system.
(14) Non-Potable Water Piping. Outlets on non-potable water lines shall be posted with a sign: "CAUTION: NON-POTABLE WATER, DO NOT DRINK."
(15) Beverage Dispensers. Except as otherwise provided in Subsection (C)(17), the potable water supply to a beverage dispenser or coffee machine shall be protected by an air gap, double check valve assembly, or vented backflow preventer consistent with ASSE 1022, installed and maintained per the manufacturer's requirements.
(16) Carbonated Beverage Dispenser. The potable water supply to a carbonated beverage dispenser shall be protected by an air gap or a reduced pressure principle assembly. The piping material installed downstream of the backflow preventer cannot be affected by carbon dioxide gas.
(17) Beverage Dispenser in Healthcare Facilities. The potable water supply to a beverage dispenser or coffee machine that is located within a healthcare facility subject to NFPA 99 shall be protected by a testable backflow prevention assembly.
(18) Deck-Mounted and Equipment Mounted Vacuum Breakers. Deck-mounted or equipment-mounted vacuum breakers shall be installed in accordance with their listing and the manufacturer's installation instructions, with the critical level not less than one inch (25.4 mm) above the flood-level rim.
(19) Protection from Fire Systems.
(a) Potable water supplies to fire protection systems that are not normally under pressure shall be protected from backflow and shall be in accordance with the requirements of the appropriate standards referenced in the Plumbing Code.
(b) Except as provided in Subsections (C)(20) and (21), potable water supplies to fire protection systems that are normally under pressure including standpipes and automatic sprinkler systems shall be protected from backpressure and backsiphonage by:
(i) a double check valve backflow prevention assembly;
(ii) a double check detector fire protection backflow prevention assembly types 1 and 2;
(iii) a reduced pressure principle backflow prevention assembly; or
(iv) a reduced pressure detector fire protection backflow prevention assembly types 1 and 2.
(20) Fire Department Connection. Where fire protection systems supplied from a potable water system include a fire department (Siamese) connection that is located less than 1,700 feet (518.2 m) from a non-potable water source that is capable of being used by the fire department as a secondary water supply, the potable water supply shall be protected by a reduced pressure principle backflow prevention assembly or a reduced pressure detector fire protection backflow prevention assembly. In this subdivision, non-potable water sources include fire department vehicles carrying water of unknown quality or water that is treated with antifreeze, corrosion inhibitors, or extinguishing agents.
(21) Chemicals. If antifreeze, corrosion inhibitors, or other chemicals are added to a fire protection system supplied from a potable water supply, the potable water system shall be protected by a reduced pressure principle backflow prevention assembly or a reduced pressure detector fire protection backflow prevention assembly.
(22) Types of Residential Systems. This subdivision applies to a stand-alone or multipurpose wet-pipe sprinkler system that does not use antifreeze. A multipurpose fire sprinkler system must provide potable water to both fire sprinklers and plumbing fixtures. A stand-alone sprinkler system must be separate and independent from the potable water system. A double check backflow prevention assembly must separate a stand-alone sprinkler system from the potable water supply.
(23) Hydraulic Design. If a backflow prevention assembly is installed in the potable water supply to a fire protection system, the hydraulic design of the system shall account for the pressure drop through the backflow assembly. If such assemblies are retrofitted for an existing fire protection system, the hydraulics of the sprinkler system design shall be checked to verify that there will be sufficient water pressure available for satisfactory operation of the fire sprinklers.
(24) Protection of Potable Mains. Private fire hydrants located at a distance from a private potable water main such that the volume of water in the hydrant lead is more than 100 gallons shall have double check backflow prevention assembly protection.
(25) Health Care or Laboratory Areas. Vacuum breakers for washer-hose bedpans shall be located not less than five feet (1,524 mm) above the floor. Hose connections in health care or laboratory areas shall be not less than six feet (1,829 mm) above the floor.
(26) Special Equipment. Portable cleaning equipment and dental vacuum pumps shall be protected from backflow by an air gap, an atmospheric vacuum breaker, a spill-resistant vacuum breaker, or a reduced pressure principle backflow preventer.
(27) Potable Water Outlets and Valves. Potable water outlets, freeze-proof yard hydrants, combination stop-and-waste valves, or other fixtures that incorporate a stop and waste feature that drains into the ground shall not be installed underground.
(28) Pure Water Process Systems. The water supply to a pure water process system, such as dialysis water systems, semiconductor washing systems, and similar process piping systems, shall be protected from backpressure and backsiphonage by a reduced pressure principle backflow preventer. However, the individual connections of the dialysis related equipment to the dialysis pure water system shall not require additional backflow protection.
(29) Garbage Can Washers. If garbage can washers are connected to a potable water supply system, the connection shall be protected against backflow with a reduced pressure principle backflow prevention assembly.
(30) Plumbing Fixture Fittings. Plumbing fixture fittings with integral backflow protection shall comply with ASME A 112.18.1/CSA B 125.1.
(31) Swimming Pools, Spas, and Hot Tubs. Potable water supply to swimming pools, spas, and hot tubs shall be protected by an air gap or a reduced pressure principle backflow preventer if the unit is equipped with a submerged fill line, or the potable water supply is directly connected to the unit circulation system.
(32) Chemical Dispensers. The water supply to chemical dispensers shall be protected against backflow as follows:
(a) If the installation of a chemical dispenser with internal backflow prevention that complies with IAPMO 1055 involves a water source from a faucet with an integrated vacuum breaker device, then a pressure bleed device conforming to IAPMO PS 104 shall be used to protect the vacuum breaker device.
(b) For all other chemical dispensers, the following assemblies, devices, or methods can be used:
(i) air gap;
(ii) atmospheric vacuum breaker;
(iii) pressure vacuum breaker;
(iv) spill-resistant pressure vacuum breaker; or
(v) reduced pressure principle backflow prevention assembly.
(33) Site Containment Backflow Prevention Requirements.
(a) A site that utilizes an alternate water source shall provide an air gap or an appropriate backflow prevention assembly located immediately downstream of all potable City water meters and City service lines to private fire lines in accordance with Table 15-1-14-C.
(b) A site that contains an actual or potential contamination hazard shall provide an air gap or an appropriate backflow prevention assembly located immediately downstream of all potable City water meters and City service lines to private fire lines in accordance with Table 15-1-14-D.
(c) A non-potable rainwater catchment or non-potable condensate collection system of 500 gallons or less does not require backflow prevention at the potable water meter.
(34) Cooling Tower Reservoirs. A water supply outlet that terminates inside the envelope of a cooling tower shall be protected with a reduced pressure principle backflow prevention assembly. A water supply outlet that terminates outside the envelope of a cooling tower shall be protected by an air gap or a reduced pressure principle backflow prevention assembly.
(35) Commercial Dishwashing Machine. The water supply to a commercial dishwashing machine shall be protected by an air gap, an atmospheric backflow preventer, a pressure vacuum breaker, a spill resistant vacuum breaker, or a device that complies with ASSE 1004.
(36) Personal Hygiene Devices. Water closets with integral personal hygiene devices shall comply with ASME A112.4.2/CSA B45.16.
TABLE 15-1-14-A
BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS
DEGREE OF HAZARD
DEVICE, ASSEMBLY, OR METHOD1 | APPLICABLE STANDARDS | LOW HAZARD | HIGH HAZARD | INSTALLATION2, 3
BACK- SIPHONAGE | BACK- PRESSURE | BACK- SIPHONAGE | BACK- PRESSURE
Air gap | ASME A112.1.2 | X | — | X | — | See Table 15-1-14-B.
Air gap fittings for use with plumbing fixtures, appliances, and appurtenances | ASME A112.1.3 | X | — | X | — | Air gap fitting is a device with an internal air gap, and typical installation includes plumbing fixtures, appliances, and appurtenances. The critical level shall not be installed below the flood level rim.
Atmospheric vacuum breaker (consists of a body, checking member and atmospheric port) | ASSE 1001 or CSA B64.1.1 | X | — | X | — | Upright position. No valve downstream. Minimum of six inches or listed distance above all downstream piping and flood level rim of receptor. 4, 5
Antisiphon fill valve (ballcocks) for gravity water closet flush tanks and urinal tanks | ASSE 1002/ASME A112.100 2/CSA B125.12 | X | — | X | — | Installation of gravity water closet flush tank and urinal tanks with the fill valve installed with the critical level not less than 1 inch above the opening of the overflow pipe. 4, 5
Vacuum breaker wall hydrants, hose bibbs, freeze resistant, automatic draining type | ASSE 1019 or CSA B64.2.1.1 | X | — | X | — | Installation includes wall hydrants and hose bibbs. Such devices are not for use under continuous pressure conditions (means of shutoff downstream of device is prohibited). 4, 5
Hose connection vacuum breakers | ASSE 1011 | X | — | X | — | Such devices are not for use under continuous pressure conditions. No valve downstream. 4, 6
Hose connection backflow preventers | ASSE 1052 | X | — | X | — | Such devices are not for use under continuous pressure conditions. 4, 6
Dual check backflow preventer wall hydrants, freeze resistant | ASSE 1053 | X | — | X | — | Such devices are not for use under continuous pressure conditions. 4
Freeze resistant sanitary yard hydrants | ASSE 1057 | X | — | X | — | Such devices are not for use under continuous pressure conditions. 4
Backflow preventer with intermediate atmospheric vent | ASSE 1012 | X | X | — | — | Installation of potable water connections to residential water boilers. No high-hazard chemicals shall be introduced into the system using such devices. Designed to operate under continuous pressure conditions. May discharge water.
Backflow preventer with intermediate atmospheric vent and pressure reducing valve | ASSE 1081 | X | X | — | — | Installation of potable water connections to residential water boilers. No high-hazard chemicals shall be introduced into the system using such devices. Designed to operate under continuous pressure conditions. May discharge water.
Backflow preventer for beverage dispensers (two independent check valves with a vent to the atmosphere) | ASSE 1022 | X | — | — | — | Installation does not include carbonated beverage machines or dispensers. Installation and maintenance must comply with manufacturer's requirements. These devices operate under intermittent or continuous pressure conditions.
Spill-Resistant Pressure Vacuum Breaker (single check valve with air inlet vent and means of field testing) | USC FCCHR 7 | X | — | X | — | Upright position. Minimum of 12 inches or listed distance above all downstream piping and flood-level rim of receptor. 5
Double Check Valve Backflow Prevention Assembly (two independent check valves and means of field testing) | USC FCCHR 7 | X | X | — | — | Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer's instructions, and not less than a 12-inch clearance at the bottom for maintenance. May need platform/ladder for test and repair. Does not discharge water.
Double Check Detector Fire Protection Backflow Prevention Assembly Types 1 & 2 (two independent check valves with a parallel detector assembly consisting of a water meter and a double check valve backflow prevention assembly and means for field testing) | USC FCCHR 7 | X | X | — | — | Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer's instructions, and not less than a 12-inch clearance at the bottom for maintenance. May need platform/ladder for test and repair. Does not discharge water. Installation includes a fire protection system and is designed to operate under continuous pressure conditions.
Pressure Vacuum Breaker Backflow Prevention Assembly (loaded air inlet valve, internally loaded check valve, and means for field testing) | X | — | X | — | Upright position. May have valves downstream. Minimum of 12 inches above all downstream piping and flood-level rim of the receptor. May discharge water.
Reduced Pressure Principle Backflow Prevention Assembly (two independently acting loaded check valves, a differential pressure relief valve and means for field testing) | USC FCCHR 7 | X | X | X | X | Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer's instructions, and not less than a 12-inch clearance at the bottom for maintenance. May need platform/ladder for test and repair. May discharge water.
Reduced Pressure Detector Fire Protection Back-flow Prevention Assembly Types 1 & 2 (two independently acting loaded check valves, a differential pressure relief valve, with a parallel detector assembly consisting of a water meter and a reduced-pressure principle backflow prevention assembly, and means for field testing) | USC FCCHR 7 | X | X | X | X | Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer's instructions, and not less than a 12-inch clearance at the bottom for maintenance. May need platform/ladder for test and repair. May discharge water. Installation includes a fire protection system and is designed to operate under continuous pressure conditions.
Laboratory faucet back-flow preventer | ASSE 035 | — | — | X | X | Installation includes laboratory faucets. Such devices are not for use under continuous pressure conditions. No valve downstream. 4
For SI units: 1 inch = 25.4 mm Table Notes: 1 See the description of devices and assemblies in this chapter. 2 Installation in pit or vault requires previous approval by the utility. 3 Refer to the general and specific requirement for installation. 4 Not to be subjected to operating pressure for more than 12 hours in a 24 hour period. 5 For deck-mounted and equipment-mounted vacuum breaker, see Section 15-1-14(C)(18). 6 Shall be installed in accordance with Section 15-1-14(C)(10). 7 Current list of approved backflow prevention assemblies, University of Southern California Foundation for Cross-Connection Control and Hydraulic Research.
TABLE 15-1-14-B
MINIMUM AIR GAPS FOR WATER DISTRIBUTION4
FIXTURES | NOT AFFECTED BY SIDEWALLS1(inches) | AFFECTED BY SIDEWALLS2(inches)
Effective openings 3 not greater than ½ of an inch in diameter | 1 | 1½
Effective openings 3 not greater than ¾ of an inch in diameter | 1½ | 2¼
Effective openings 3 not greater than 1 inch in diameter | 2 | 3
Effective openings 3 greater than 1 inch in diameter | Two times the diameter of the effective opening | Three times the diameter of the effective opening
Notes: 1. Sidewalls, ribs, or similar obstructions do not affect air gaps if spaced from the inside edge of the spout opening a distance exceeding three times the diameter of the effective opening for a single wall, or a distance exceeding four times the effective opening for two intersecting walls. 2. Vertical walls, ribs, or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening other than specified in Footnote 1 above affect air gaps. The effect of three or more such vertical walls or ribs has not been determined. In such cases, the air gap shall be measured from the top of the wall. 3. The effective opening shall be the minimum cross-sectional area at the seat of the control valve or the supply pipe or tubing that feeds the device or outlet. If two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas of the individual supply lines or the area of the single outlet, whichever is smaller. 4. Air gaps less than one inch (25.4 mm) shall be approved as a permanent part of a listed assembly that has been tested under actual backflow conditions with vacuums of 0 to 25 inches of mercury (85 kPa).
TABLE 15-1-14-C
ALTERNATE WATER SITE CONTAINMENT BACKFLOW PREVENTION
List of Auxiliary Water Sources and Uses 1 | Backflow prevention required at potable water connection | Backflow protection required at point of interconnection with potable water
Domestic water meter | Irrigation water meter 2 | City service to private fire mains 2, 3, 4, 5
Lake/River water | RP | RP | DC | RP
Well water | RP | RP | DC | RP
Condensate water | Gravity | - | DC 5 | DC | RP
Pumped | RP | RP | DC | RP
Rainwater | Gravity | - | DC 5 | DC | RP
Pumped | RP | RP | DC | RP
Assemblies Gray water | Gravity | - | DC 5 | DC | AG
Pumped | RP | RP | DC | AG
Reclaimed water 6 | RP | RP | DC | AG
Other water supply 7 | RP | RP | DC | AG
Table Notes: RP: Reduced pressure zone backflow prevention assembly. DC: Double check backflow prevention assembly. AG: Air gap.
1. If multiple sources of alternate water are used, all backflow protection must meet the most stringent requirements of the sources used.
2. A backflow prevention assembly installed at the potable service connection of a site served by an alternate water source must have an annual operational test.
3. A new backflow prevention assembly installed in an existing fire system may result in the need to re-calculate fire system design specifications due to backflow preventer pressure losses.
4. A backflow prevention assembly installed in an un-metered fire system is required to be a detector assembly.
5. These backflow prevention assemblies are required regardless of the presence of alternate water.
6. When a chemical addition system is used (e.g., fertigation) a DC will be required on the reclaimed water service connection.
7. Other water supply includes all other alternate waters not listed in the table.
TABLE 15-I-14-D
SITE CONTAINMENT FOR PREMISES ISOLATION
Description of Premises requiring site containment3 | Hazard Assessment | Required backflow prevention at meter/s1 | Required backflow prevention at private unmetered fire mains1, 2
Aircraft, automotive and missile plants | Health | RP or AG | DCDA
Animal feedlots | Health | RP or AG | DCDA
Breweries | Health | RP or AG | DCDA
Canneries, packing houses, rendering plants, slaughterhouses | Health | RP or AG | DCDA
Commercial car washes | Health | RP or AG | DCDA
Commercial laundries | Health | RP or AG | DCDA
Cold storage facilities | Health | RP or AG | DCDA
Dairies | Health | RP or AG | DCDA
Docks, dockside facilities, marinas | Health | RP or AG | DCDA
Dye works | Health | RP or AG | DCDA
Food and beverage processing plants | Health | RP or AG | DCDA
Hospitals, morgues, mortuaries, medical clinics, dental clinics, veterinary clinics, autopsy facilities, sanitariums, and medical labs | Health | RP or AG | DCDA
Metal manufacturing, cleaning, processing, and fabrication plants | Health | RP or AG | DCDA
Microchip fabrication facilities | Health | RP or AG | DCDA
Paper and paper products plants | Health | RP or AG | DCDA
Petroleum processing or storage facilities | Health | RP or AG | DCDA
Plants using radioactive material | Health | RP or AG | DCDA
Plating or chemical plants | Health | RP or AG | DCDA
Power plants | Health | RP or AG | DCDA
Restricted, classified, or other closed facilities | Health | RP or AG | DCDA
Rubber plants | Health | RP or AG | DCDA
Sewage lift stations | Health | RP or AG | DCDA
Sewage treatment plants | Health | RP or AG | DCDA
Steam plants | Health | RP or AG | DCDA
Sites where highest outlet is 80' or more above the meter | Nonhealth | DC | DCDA
Table Notes: RP: reduced pressure principle backflow prevention assembly. DC: double check backflow prevention assembly AG: air gap. 1 Backflow preventers shall be tested annually. 2 A backflow prevention assembly installed on an existing fire system may result in the need to re-calculate fire design specifications due to pressure loss through the backflow preventer. 3 This table lists many common hazards. It is not an all-inclusive list of the hazards which may be found connected to public water systems.
Source: Ord. No. 20250410-002, Pt. 1, 4-21-25.