IDENTIFICATION OF POTABLE AND NON-POTABLE WATER SYSTEMS.
Austin City Code § 15-1-13
in effect§ 15-1-13 - IDENTIFICATION OF POTABLE AND NON-POTABLE WATER SYSTEMS.
(A) Except as provided in Subsection (B), if potable water and non-potable water systems are installed on the same site, the customer shall label and identify each system in accordance with the following requirements:
(1) Each water system shall be identified with a colored pipe or sleeve and coated with paints, wraps, and materials that are compatible with the piping.
(2) Potable water system pipes shall be identified with a green background and white lettering.
(3) Except as otherwise provided by Subsections (A)(6), (7) and (8), a non-potable water system shall have a yellow background with black uppercase lettering and be marked with the words: "CAUTION: NON-POTABLE WATER, DO NOT DRINK".
(4) Potable or non-potable water systems shall be identified in a manner that designates the liquid being conveyed and shows the direction of normal flow. The minimum size of the letters and length of the color field shall comply with Table 15-1-13-A.
(5) For piping above grade, the background color and the required information shall be indicated every 20 feet (6,096 mm), on both sides of a wall or partition penetrated by the piping, and at least once in every story height traversed by the risers. The labeling shall be visible from the floor level. For piping below grade, the background color and the required information must be indicated every five feet (1,524 mm).
(6) All reclaimed water piping or onsite water reuse system piping inside a building shall be purple pipe or painted purple (Pantone colors No. 5-12, 5-22C or equivalent).
(7) All buried reclaimed water piping or onsite water reuse system water piping must be either manufactured in purple, painted purple, taped with purple metallic tape, or bagged in purple.
(8) An alternate water source system shall have a purple (Pantone colors No. 5-12, 5-22C or equivalent) background with uppercase black lettering and shall be field or factory marked as follows:
(a) An onsite water reuse system shall be marked with the words: "CAUTION: NON-POTABLE ONSITE WATER REUSE SYSTEM, DO NOT DRINK" in uppercase black letters.
(b) A reclaimed water system shall be marked with the words: "CAUTION: NON-POTABLE RECLAIMED WATER SYSTEM, DO NOT DRINK" in uppercase black letters.
(c) Other alternate water systems shall be marked with the words: "CAUTION: NON-POTABLE ALTERNATE WATER SOURCE, DO NOT DRINK" in uppercase black letters.
(B) A water system is not required to be labeled if:
(1) the system is for potable water inside a building and the non-potable system does not enter the building; or
(2) the below grade pipe and components of an existing irrigation system are converted to a reclaimed, onsite water reuse system water source, or other water sources and have not been disturbed.
(C) Any repair, addition or alteration to an irrigation system, and all pipe and components located above grade or accessible within a subsurface vault of an existing irrigation system converted to alternate water, must be identified consistent with Subsection (A) and 30 T.A.C. Section 344.65(3).
(D) Identification of the discharge side is not required for vacuum breakers or backflow preventers installed with fixtures listed in Chapter 17 of the adopted Plumbing Code.
(E) Each outlet on a non-potable water line that is used for special purposes shall be posted with a sign with black uppercase lettering as follows: "CAUTION: NON-POTABLE WATER, DO NOT DRINK".
TABLE 15-1-13-A
MINIMUM LENGTH OF COLOR FIELD AND SIZE OF LETTERS
OUTSIDE DIAMETER OF PIPE OR COVERING (inches) | MINIMUM LENGTH OF COLOR FIELD (inches) | MINIMUM SIZE OF LETTERS (inches)
½ to 1¼ | 8 | ½
1½ to 2 | 8 | ¾
2½ to 6 | 12 | 1¼
8—10 | 24 | 2½
OVER 10 | 32 | 3½
Source: Ord. No. 20250410-002, Pt. 1, 4-21-25.
Source: City of Austin, City Code and City Charter (Municode Library, library.municode.com)URL: https://library.municode.com/tx/austin/codes/code_of_ordinances?nodeId=TIT15UTRE_CH15-1CRNNRE_ART2CRNNCOPR_S15-1-13IDPONTAWASYFetched: 10/27/2026