Ductile iron pipe.
Omaha Municipal Code § 49-812
in effectSec. 49-812. - Ductile iron pipe.
All ductile iron water pipe shall conform to ANSI A21.51 and the following provisions:
(a) Pipe used for water main (service) shall be at least class 52, cement lined in compliance with the AWWA C104.
(b) Pipe used for building drains and building sewers shall be at least class 50 pipe with fittings conforming to ASTM C600.
(Ord. No. 40524, § 1, 10-20-15)