Protection required; installation.
Round Rock Code of Ordinances § 44-177
in effectSec. 44-177. - Protection required; installation.
(a) The assembly protection which is required under this article shall be any of the duly authorized assemblies listed in the Uniform Plumbing Code, or as determined by the director. Each assembly must be approved in writing by the director in conjunction with the chief building inspector of the city prior to installation. Failure to obtain such written approval prior to installation of the assembly may result in the assembly failing to meet final approval by the director. The director shall determine the type and location of assembly to be installed within the area served by the city. An assembly shall be required in each of the following circumstances, but the director is not limited to requiring the installation of an assembly only in the following circumstances:
(1) The nature and extent of any activity on or near the premises, or the materials used in connection with any activity on or near the premises, or materials stored on or near the premises, may contaminate or pollute the potable water supply.
(2) Premises having any one or more cross connections identified or one or more cross connections present on the premises.
(3) One or more cross connections are present on the premises and the cross connections are protected by an atmospheric vacuum breaker device (AVB).
(4) Internal cross connections are present that are not correctable.
(5) Intricate plumbing arrangements are present which make it impractical to ascertain whether cross connections exist.
(6) There is a repeated history of cross connections being established or re-established on the premises.
(7) There is unduly restricted entry so that inspections for cross connections cannot be made with sufficient frequency to assure that cross connections do not exist.
(8) Materials are being used on the premises such that, if backflow should occur, a health hazard may result.
(9) Installation of an approved backflow prevention assembly is deemed to be necessary to accomplish the purpose of these regulations in the sole judgment of the city.
(10) An appropriate cross connection survey report form has not been filed with the public works department of the city after a request by the city.
(11) A fire sprinkler system on the premises is connected to the city's water system.
(12) All new construction, if deemed necessary as a result of the customer service inspection referred to in section 44-182. The type of assembly required shall be commensurate with the degree of hazard as determined by the director.
(13) When a building is constructed on commercial premises, and the end use of such building is not determined or could change, a reduced pressure principle backflow prevention assembly must be installed at the service connection that supplies water for public domestic use.
(14) Any used water return system is present on the premises.
(15) In the event a point-of-use assembly has not had the testing or repair done as required by this section, a premises isolation assembly will be required.
(16) If it is determined that additions or alterations have been made to the plumbing system without obtaining proper permits, premises isolation may be required.
(17) All multistory buildings or any building with a booster pump or elevated storage tank.
(18) Retrofitting will be required on all high hazard connections, and in additional circumstances in which the city deems it necessary to retrofit.
(b) All assemblies installed after the effective date of the ordinance from which this article is derived shall be installed in a manner designed to facilitate ease of inspection by the director of the city. Any currently installed assemblies that, in the opinion of the director, are located in inaccessible locations, or where the tester is subjected to physical danger, shall be relocated to location approved in writing by the director.
(Code 1995, § 10.705; Ord. No. O-2015-2423, § I, 5-14-2015; Ord. No. O-2024-266, § XVII, 9-26-2024)