§ 11-107 — Distance from buildings
Code of Ordinances, City of Denton, Texas (Supp. No. 37, Update 1: codified through Ordinance No. 26-296 adopted March 24, 2026) · Denton City Code § 11-107
Corpus is an independent public-information project, not the official City of Denton website. Stable reference: corpuslaw.us/code/9357a1e9-08ac-45b2-b437-3a3801b2282a
Sec. 11-107. - Distance from buildings.
(a) The fire lane shall be extended to within one hundred (100) feet of maximum hose distance from all portions of the exterior walls of the first story of all buildings, except one and two family dwellings. For buildings equipped with an automatic sprinkler system throughout, the fire lane shall extend to within fifty (50) feet of the fire department hose connection. (b) Where the fire lane cannot be provided to within one hundred (100) feet of maximum hose distance from all portions of the exterior walls of the first story of a building, or where the building height is thirty (30) feet or more, an approved fire protection system shall be provided as required and approved by the fire marshal, and adequate access roadways extending to within fifty (50) feet of the entire front of the building shall be provided for fire equipment access to the building as required and approved by the fire marshal. (c) If a building is equipped with an automatic sprinkler, the fire lane may be extended to be within one hundred fifty (150) feet of all exterior walls of the first story of a building.
(Ord. No. 91-065, § V, 4-30-91; Ord. No. 95-260, § III, 12-19-95)