Sizing
Tyler City Code § 19-123
in effectSec. 19-123 Sizing
a. In approving a customer's plumbing or GRD design, the City does not accept liability for the failure of a system to adequately treat wastewater. It is the responsibility of the Operator and/or contractors to insure the appropriate level of treatment necessary for compliance.
b. No GRD with less than 375 pound (750 gallon) total capacity will be approved for installation by the City unless acceptable engineering calculations, sealed by a professional engineer registered in the state of Texas, and demonstrating that a smaller size has satisfactory capacity, are provided by the Operator to the City, and are approved by the City prior to installation. The City retains sole discretion to approve or deny approval of GRD with less than 375 pound (750 gallon) total capacity in all circumstances, even in the event such engineering calculations are provided.
c. In no instance shall GRD of less than 250 pound (500 gallon) capacity be approved.
d. Food Service Establishment (FSE) GRD(s) shall be sized in accordance with the number of kitchen plumbing fixtures and/or those that could introduce grease into the POTW (e.g. vent hood), in the facility, so as to provide a minimum detention time of thirty (30) minutes. Plumbing fixtures include the following: hand sink, vegetable preparation sink, 2 or 3 compartment sink, mop sink, other sink types, dishwasher, floor drain(s), and trough drain(s). All floor drains shall count as one (1) fixture. Generators with dishwashers shall have a 750 pound (1500 gallon) or larger GRD.
e. Non-FSE(s) shall be sized according to the size of the water meter servicing the property.
f. GRD sizing worksheets for both FSE(s) and Non-FSE(s) are available from the City.
g. The Managing Director may require a larger capacity GRD for Generators that may introduce larger quantities of FOG by frying, grilling, or other cooking processes. The Managing Director may also require a larger capacity GRD for Generators that have periodic drain backups or cause periodic sewer line stoppages attributed to excessive FOG and/or grit.
Source: City of Tyler, Texas, Code of Ordinances and Charter (American Legal Publishing, codelibrary.amlegal.com)URL: https://codelibrary.amlegal.com/codes/tyler/latest/tyler_tx/0-0-0-104689Fetched: 11/14/2026