Omaha Municipal Code § 49-1420 General.
Sec. 49-1420. - General.
Cleanout plugs may be brass, cast-iron or plastic with standard iron pipe size threaded plugs. Cleanouts in interceptors shall be standard pipe threaded brass or cast-iron plugs. Loose-plate or bolted-cover cleanouts are not permitted. Cleanout size shall comply with Table 49-1420.
Table 49-1420
Cleanouts
Size of Pipe (Inches) | Size of Cleanout (inches) | Threads Per Inch
1½ | 1½ | 11½
2 | 1½ | 11½
2½ | 2½ | 8
3 | 2½ | 8
4 and larger See Note 1 | 3½ | 8
Note 1: A three-inch test tee with a three-inch opening may serve as a cleanout for a four-inch building drain in single-family dwellings only.
(Ord. No. 40524, § 1, 10-20-15; Ord. No. 42654, § 42, 8-13-21)