§ 9.52.080.54 — Section 913.2.4 Fire Pump Power Supply Disconnect, Added
El Paso City Code (Supp. No. 95, Update 4: codified through Ordinance No. 019889, enacted June 23, 2026) · El Paso City Code § 9.52.080.54
Corpus is an independent public-information project, not the official City of El Paso website. Stable reference: corpuslaw.us/code/ab1d5ac5-c447-460a-95f2-1b1d6c134287
9.52.080.54 - Section 913.2.4 Fire Pump Power Supply Disconnect, Added.
913.2.4 Fire Pump Power Supply Disconnect. A Mandatory Fire Pump power supply disconnect is required for all fire pump controllers. This disconnect shall not be located in the fire pump room and will be approved by the AHJ. Markings for the disconnecting means shall be in accordance with article 695.4 of the National Electrical Code (NEC).
(Ord. No. 019521, § 1, 7-5-2023)
Ask a question about El Paso law