Sec. 49-1562. - Private fire hydrants.
Private fire hydrants shall conform to Metropolitan Utilities District Rules and Regulations Part VII and the following: (a) MUD's fire hydrant specifications, MUD 100, and installed according to manufacturer instructions. (b) An approved valve shall be installed on the hydrant branch to isolate the hydrant. (c) Connected to the water purveyor's system or master service by a six-inch diameter or larger pipe. (d) Basic maintenance of private fire hydrants that consists of replacement of parts worn by normal use. (e) Bottom of the breakaway flange shall be a maximum of four inches from the ground. (f) The pumper nozzle cap shall face the street. (g) Hydrants that repair parts cannot be obtained within 30 days shall be replaced. (h) Repair, testing or replacement of hydrants shall be at the owner's expense.
(Ord. No. 40524, § 1, 10-20-15)