§ 230.85
New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 230.85
Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/be161bd5-f352-4582-94a2-735d34ee68f4
Section 230.85
Section 230.85 – Add an Exception at the end of Section 230.85 to read as follows: Exception: If the emergency disconnecting means cannot be located in a readily accessible outdoor location, or if the utility metering equipment is located indoors, 1 of the following disconnecting means shall be permitted: 1. A remote disconnecting means provided by the utility 2. An indoor shunt-trip disconnecting means with the control device located in a readily accessible outdoor location and marked, “Remote Emergency Disconnect” 3. An approved equivalent means.