Same—Specifications.
Chandler City Code § 52-4
in effect52-4. - Same—Specifications.
A. It shall be the responsibility of the designated City Engineer to approve or direct the type and size of water meter to be installed based on the proposed use. All water meters of three (3) inches or over in size shall be compound meters unless otherwise approved by the designated City Engineer.
B. Multiple meter installations in a manifold system are permissible, but each meter so installed shall be equipped with a check valve installed by the owner on the customer side of the meter.
C. Residential meter installations serving both domestic and fire sprinkler systems shall be equipped with a check valve installed by the owner on the customer side of the meter in addition to the check valve in the sprinkler riser.
D. The service line from the main to multiple meter installations must be sized so as to carry a quantity of water equal to the sum of the capacity of all the multiple meters.
(Ord. No. 659, § 1, 12-11-75; Ord. No. 927, § 1, 2-12-81; Ord. No. 1060, § 1, 10-6-82; Ord. No. 1378, § 4, 10-25-84; Ord. No. 1989, § 2, 8-22-88; Ord. No. 3060, § 2, 11-18-99; Ord. No. 4802, § 2(Exh., § 35), 4-26-18)