Sec. 22-7-3. - Definitions.
The following words, terms, and phrases, when used in this article, shall have the meanings ascribed to them in this section, except where the context clearly indicates a different meaning:
Air gap means a physical separation sufficient to prevent backflow between the free-flowing discharge end of the potable water system and any other system. Physically defined as a distance equal to twice the diameter of the supply side pipe diameter but never less than one inch.
Approved means accepted by the director of the public works department as meeting an applicable specification stated or cited in this regulation, or as suitable for the proposed use.
Atmospheric vacuum breaker means a device which prevents back-siphonage by creating an atmospheric vent when there is either a negative pressure or subatmospheric pressure in a water system.
Auxiliary water supply means any water supply, on or available, to the premises other than the city's approved public potable water supply.
Backflow means the flow of water or other liquids, mixtures or substances, under positive or reduced pressure in the distribution pipes of a potable water supply from any source other than its intended source.
Backflow preventer means a device or means designed to prevent backflow or back-siphonage. Most commonly categorized as air gap, reduced pressure principal device, double check valve assembly, pressure vacuum breaker, atmospheric vacuum breaker, hose bibb vacuum breaker, residential dual check, double check with intermediate atmospheric vent, all of which terms are elsewhere defined herein.
Backpressure means a condition in which the owner(s) system pressure is greater than the suppliers system pressure.
Back-siphonage means the flow of water or other liquids, mixtures or substances into the distribution pipes of a potable water supply system from any source other than its intended source caused by the sudden reduction of pressure in the potable water supply system.
City means the City of Biloxi, Mississippi.
Containment means a method of backflow prevention which requires a backflow preventer at the water service entrance.
Contaminant means a substance that will impair the quality of the water to a degree that it creates a serious health hazard to the public leading to poisoning or the spread of disease.
Cross-connection means any actual or potential connection between the public water supply and a source of contamination or pollution.
Department or public works department means the City of Biloxi, Mississippi, Department of Public Works.
Department of health means the state department of health division of water supply.
Director of public works or director means the Director of the Department of Public Works of the City of Biloxi, Mississippi, or his designated representative.
Double check valve assembly means an assembly of two independently operating spring loaded check valves with tightly closing shut off valves on each side of the check valves, plus properly located test cocks for the testing of each check valve.
Double check valve with intermediate atmospheric vent means a device having two spring loaded check valves separated by an atmospheric vent chamber.
Fixture isolation means a method of backflow prevention in which a backflow preventer is located to correct a cross connection at an in-plant location rather than at a water service entrance.
Health hazard (high hazard) means contamination with the potential to endanger the health and well being of the water customer or owner.
Hose bibb vacuum breaker means a device which is permanently attached to a hose bibb and which acts as an atmospheric vacuum breaker.
Nonpotable water means water not acceptable for human consumption or of unknown quality.
Non-health hazard (low hazard) means not harmful to health, but would still be objectionable.
Owner means any person who has legal title to, or license to operate or habitat in, a property upon which a cross-connection inspection is to be made or upon which a cross connection is present.
Person means any individual, partnership, company, public or private corporation, political subdivision, department, agency or instrumentality of the state or the United States or any other legal entity.
Permit means a document issued by the director of public works or his designated representative of the city which allows the use of a backflow preventer.
Pollutant means a foreign substance that, if permitted to get into the public water system, will degrade its quality so as to constitute a high hazard, or impair the usefulness or quality of the water to a degree which does not create an actual hazard to the public health but which does adversely and unreasonably affect such water for domestic use.
Potable water means water that is acceptable for human consumption.
Pressure vacuum breaker means a device containing one or two independently operated spring loaded check valves and an independently operated spring-loaded air inlet valve located on the discharge side of the check or checks. Device includes tightly closing shut-off valves on each side of the check valves and properly located test cocks for the testing of the check valve(s).
Reduced pressure principal backflow preventer means an assembly consisting of two independently operating approved check valves with an automatically operating differential relief valve located between the two check valves, tightly closing shut-off valves on each side of the check valves plus properly located test cocks for the testing of the check valves and the relief valve.
Residential dual check means an assembly of two spring loaded, independently operating check valves without tightly closing shut-off valves and test cocks. Generally employed immediately downstream of the water meter to act as a containment device.
Water service entrance means that point in the owner(s) water system beyond the sanitary control of the city; generally considered to be the outlet end of the water meter and always before any unprotected branch.
(Ord. No. 1889, § 1, 8-3-99)