For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 701.5

New York City Administrative Code (current through L.L. 2026/147, enacted September 12, 2026, and amendments effective through October 10, 2026) · NYC Electrical Code § 701.5

Corpus is an independent public-information project, not the official City of New York website. Stable reference: corpuslaw.us/code/c6a8ab9c-5a57-4242-859c-597e05dfe58a

Section 701.5

Section 701.5 – Add new Sections 701.5(E) and 701.5(F) to read as follows: (E) Manual Operation. Means shall be provided to manually operate the switch without hazard to personnel. (F) Permanent Connections for Portable Generators. Where a permanent connection is made for a portable generator, a disconnecting means and overcurrent protection shall be provided at the point of connection for the portable generator. Capacity shall not exceed the capacity of the permanent installation.

Ask a question about New York law

Corpus searches the New York sections it holds and shows the ones that match, with their citations. Free, no sign-in.