Section 701.5
Section 701.5 – Add new Sections 701.5(E) and 701.5(F) to read as follows: (E) Manual Operation. Means shall be provided to manually operate the switch without hazard to personnel. (F) Permanent Connections for Portable Generators. Where a permanent connection is made for a portable generator, a disconnecting means and overcurrent protection shall be provided at the point of connection for the portable generator. Capacity shall not exceed the capacity of the permanent installation.