509.1340. - Cross-connections and backflow prevention in potable water system.
(a) If an on-premises survey is necessary to evaluate cross-connection hazards, the director shall provide written notice to the customer and require the survey to be completed within sixty (60) days. The customer may have the division conduct the survey at no cost or may choose to hire and pay an independent company who utilizes currently accredited ASSE 5120 backflow prevention surveyors. (b) Both the director and the customer shall be notified of the finding of any on premises cross connection or backflow prevention surveys, including the degree of hazard and the corrective actions to be taken. If there is imminent danger, the cross-connection hazard shall be addressed immediately, and the water service may be shut off until the hazard is eliminated. Other corrective actions shall be taken within sixty (60) days of the survey and reported to the division when complete. (c) If backflow prevention is required to protect the public water system, the director shall notify the customer and specify the requirements. The customer shall immediately install such backflow prevention. The cost of installing, testing, repairing, and maintaining the backflow assembly shall be the responsibility of the customer and in accordance with Chapter 91 and the current utility rates set by City Council resolution. (d) If the required backflow prevention is not installed, tested, maintained, and repaired, or if the required backflow prevention is removed or bypassed, penalties may be applied in accordance with the current utility rates set by city council resolution. Noncompliance may result in a water service shut off. Shut off and turn on fees will be charged. Service will not be turned on again until defects are corrected. All violations shall be reported to the Director of Regulatory Services for the purpose of conformance with Chapter 244 of this Code of Ordinances. (e) Maintenance and repair work on backflow devices shall be performed by a licensed master plumber, or by a licensed journeyman plumber, under the supervision of a master plumber (Minn. Stat. § 326B.46), who is also a certified backflow prevention assembly tester/rebuilder.
(Ord. No. 2022-024, § 4, 5-26-22; Ord. No. 2025-014, § 19, 2-27-25)
Ask a question about Minneapolis law
Corpus searches the Minneapolis sections it holds and shows the ones that match, with their citations. Free, no sign-in.