§ 10.36.210 — Location of Gas Pipe

Spokane Municipal Code; partial · SMC 10.36.210 · Effective

Corpus is an independent public-information project, not the official City of Spokane website. Stable reference: corpuslaw.us/code/ded4144b-376b-4ceb-8619-0488f3a0b3cb

Section 10.36.210 Location of Gas Pipe

Subject to the direction of the director of engineering services in particular cases, every gas franchisee must comply with the following standards for the location of gas system piping: A. Pipes are placed in alleys or utility easements. B. Pipes are placed in the southerly or westerly side of alleys or streets. C. Pipes have a lateral clearance of four feet from water mains and twelve inches from all other subsurface structures and a vertical clearance of twelve inches from another pipe. D. Pipes have at least thirty inches of cover or, when in rock, twenty-four inches if properly cushioned. E. Gas service lines do not occupy the same ditch with water service lines. F. Pipe is laid in the center of the trench as nearly as possible to equalize the pressure load from backfilling.

Date Passed: Monday, June 4, 2007 Effective Date: Wednesday, July 11, 2007 ORD C34041 Section 1 (Recodification)

Ask a question about Spokane law

Corpus searches the Spokane sections it holds and shows the ones that match, with their citations. Free, no sign-in.