16.08.012 - Amendments to the 2024 International Building Code.
The following amendments, deletions or additions to the 2024 Edition of the International Building Code are adopted by reference as fully as though copied into said Building Code and thereby made a part of the Building Code.
A. Section 101.1 of the 2024 Edition of the International Building Code is hereby amended by deleting Section 101.1 and substituting the following:
These regulations shall be known as the Building Code of Metropolitan Nashville and Davidson County, hereinafter referred to as "this code."
B. The 2024 Edition of the International Building Code is hereby amended by deleting Sections 102 through 116.5 in their entirety.
C. Section 201 of the 2024 Edition of the International Building Code is hereby amended by adding the following new Section 201.5 to Section 201:
201.5 Interchangeability with The International Codes. The International Property Maintenance Code shall be construed to mean the Property Standards Code of the Metropolitan Government. The International Private Sewage Disposal Code shall be construed to mean the Subsurface Sewage Disposal Systems Code of the Metropolitan Government. The ICC Electrical Code shall be construed to mean the National Electrical Code.
D. Section 202 of the 2024 Edition of the International Building Code is hereby amended by adding the following new definitions:
BED AND BREAKFAST HOMESTAY — means a private home, inn, or other unique residential facility located in a structure of historical significance as defined in Tennessee Code Annotated Section 68-14-503(3) offering bed and breakfast accommodations and one (1) daily meal and having less than four (4) guest rooms furnished for pay, with guests staying not more than fourteen (14) days, and where the innkeeper resides on the premises or property, or immediately adjacent to it. Guest rooms shall be established and maintained distinct and separate from the innkeeper's quarters.
BREEZEWAY — a covered connector between two buildings or structures, open at each end but less than 50 percent open, located at, above, or below grade level, that may be used as a means of egress from a building or structure.
BOARD — shall mean the Metropolitan Board of Fire and Building Code Appeals.
BUILDING OFFICIAL — shall mean the Director of the Metropolitan Department of Codes Administration, his deputy or duly authorized representative.
CODE OFFICIAL - shall mean the Director of the Metropolitan Department of Codes Administration, his deputy or duly authorized representative.
DIRECTOR — shall mean the Director of the Metropolitan Department of Codes Administration, his deputy or duly authorized representative.
NORMAL MAINTENANCE REPAIRS — shall be defined as repairs to an existing building or structure, including but not limited to exterior and interior painting, papering, glazing of windows and doors, floor finishing, minor repairs to chimneys, stairs, porches, underpinning, and repairs to an existing roof not to exceed 33 percent of the roof area.
TEMPORARY — shall mean not more than 90 calendar days.
E. Section 310.4, R-3 of the 2024 Edition of the International Building Code is hereby amended by adding the following to Section 310.4:
Bed and breakfast homestays are classified as R3.
F. Section 423 Storm Shelters of the 2024 Edition of the International Building Code is hereby amended by deleting Section 423 in its entirety.
G. Section 502.1 of the 2024 Edition of the International Building Code is hereby amended by deleting Section 502.1 and substituting the following:
502.1. Premises Identification. All buildings and structures within Metropolitan Nashville and Davidson County shall have approved address numbers posted in accordance with the following:
1. Residences are to have their numbers at least three (3) inches in size, on a contrasting background, and in a position to be plainly visible and legible from the street or road fronting the property. The numbers may be attached to the residence or the mailbox, if the mailbox is next to the street.
2. Numbers posted on the outside of nonresidential buildings must be six inches, or larger, on a contrasting background, and in a position to be plainly visible and legible from the street or road fronting the premises. Numbers posted on interior doors or spaces (such as a lease space in a mall) must be at least three inches in size.
3. Multifamily buildings shall have their numbers displayed to be plainly visible and legible, on a contrasting background, and a minimum size of six inches in height. Identifying numbers, at least three inches in height, shall also be posted on or at the doors of individual dwelling units.
H. Sections 907.2.11.2 through 907.2.11.4 of the 2024 Edition of the International Building Code are hereby amended by deleting Sections 907.2.11.2 through 907.2.11.4 and substituting the following:
907.2.11.2 Groups R-2, R-3, R-4 and I-1. Single-or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1, regardless of occupant load in the following locations:
1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.
2. In each room used for sleeping purposes.
3. In each story within a dwelling unit, including basements, garages and cellars but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
Exception: Heat detectors may be substituted for smoke detectors installed in cellars and attached garages.
907.2.11.2.1 Additions, alterations or repairs to Group R. Where an addition, alteration or repair to an individual dwelling unit or guestroom in Group R requires a permit, smoke alarms shall be installed within that individual dwelling unit or guestroom in accordance with this section. Where one or more sleeping rooms are added or created in an existing Group R, smoke alarms shall be installed in accordance with this section.
Exception: Repairs to the exterior surfaces of occupancies in Group R are exempt from the requirements of this section.
I. Section 1006.3.4 of the 2024 Edition of the International Building Code is hereby amended by deleting Section 1006.3.4 Single Exits in its entirety and substituting the following:
1006.3.4 Single Exits. A single exit or access to a single exit shall be permitted from any story or occupied roof where one of the following conditions exists:
1. The occupant load, number of dwelling units and exit access travel distance within the portion of the building served by the single exit do not exceed the values in Table 1006.3.4(1) or 1006.3.4(2).
2. Rooms, areas and spaces complying with Section 1006.2.1 with exits that discharge directly to the exterior at the level of exit discharge, are permitted to have one exit or access to a single exit.
3. Parking garages where vehicles are mechanically parked shall be permitted to have one exit or access to a single exit.
4. Group R-3 and R-4 occupancies shall be permitted to have one exit or access to a single exit.
5. Individual single-story or multistory dwelling units shall be permitted to have a single exit or access to a single exit from the dwelling unit provided that both of the following criteria are met:
1. The dwelling unit complies with Section 1006.2.1 as a space with one means of egress.
2. Either the exit from the dwelling unit discharges directly to the exterior at the level of exit discharge, or the exit access outside the dwelling unit's entrance door provides access to not less than two approved independent exits.
6. Not more than six stories of Group R-2 occupancy are permitted to be served by an interior or exterior single exit under the following conditions:
1. The building has not more than six stories above grade plane.
2. There shall be no more than four dwelling units on any floor.
3. The building does not contain a boarding house.
4. The building shall also be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. NFPA 13 sprinklers shall be used in all habitable spaces in each dwelling unit.
5. There shall be no more than one single exit stairway condition on the same parcel. Single exit stair buildings will be restricted to any location within the UZO district.
6. An exterior stairway or interior exit stairway shall be provided with a minimum 2-hour rated fire separation. The interior exit stairway, including any related exit passageway, shall be pressurized in accordance with Section 909.20.6.
7. A 1-hour rated corridor shall separate each dwelling unit entry/exit door from the door to an interior exit stairway, including any related exit passageway, on each floor. Dwelling unit doors shall be 45-minute fire-resistance rated doors. Dwelling Unit Doors shall not open directly into an interior exit stairway. Dwelling unit doors are permitted to open directly into an exterior stairway.
8. There shall be no more than 20 feet (6096 mm) of travel the exit stairway from the entry/exit door of any dwelling unit.
9. Travel distance measured in accordance with Section 1017 shall not exceed 125 feet.
10. Other occupancies are permitted in the same building provided they comply with all the requirements of this code. Other occupancies shall not communicate with the Group R occupancy portion of the building or with the single-exit stairway.
Exception: Parking garages and occupied roofs accessory to the Group R occupancy are permitted to communicate with the exit stairway. Each of these components will be considered one of the levels in the building.
11. The exit serving the Group R occupancy shall not discharge through any other occupancy, including an accessory parking garage.
12. There shall be no openings within 10 feet (3048 mm) of unprotected openings into the stairway other than required exit doors having a one-hour fire-resistance rating.
13. The stairway shall be a minimum of 54" clear for egress and ingress.
The area under the lowest stair flight shall be permanently enclosed without any allowable storage under the stair.
J. Section 1015.4 of the 2024 Edition of the International Building Code is hereby amended by adding the following exception number 7.
7. From the walking surface to the first element, the guard shall not have openings that allow the passage of a sphere 2 inches in diameter.
K. The 2024 Edition of the International Building Code is hereby amended by deleting Section 1612- Flood Loads.
L. Section 2902.3.4 of the 2024 Edition of the International Building Code is hereby amended by adding the following to the end of Section 2902.3.4.
Restaurants other than food tenants in the food court shall have the required facilities installed within their tenant space.
M. Section 3103 of the 2024 Edition of the International Building Code is hereby amended by deleting Section 3103 and substituting the following:
3103 TEMPORARY STRUCTURES
3103.1 General. The provisions of this section shall apply to structures erected for a period of 90 days or less. Tents and other membrane structures erected for a period of 90 days or less shall comply with the Metropolitan Fire Code. Structures erected for a longer period of time shall comply with applicable sections of this code.
Exception: Provisions of the Metropolitan Fire Code shall apply to tents and membrane structures erected for a period of 90 days or less.
3103.1.1 Permit required. Temporary structures that cover an area in excess of 120 square feet (11.16 m2), including connecting areas or spaces with a common means of egress or entrance which are used or intended to be used for the gathering together of ten or more persons, shall not be erected, operated or maintained for any purpose without obtaining a permit from the building official.
N. Section 3202.3.1 of the 2024 Edition of the International Building Code is hereby amended by deleting Section 3202.3.1 and substituting the following:
3202.3.1 Awnings, canopies, marquees and signs. Awnings, canopies, marquees and signs shall be constructed so as to support applicable loads as specified in Chapter 16. Awnings, canopies, marquees and signs with less than 15 feet (4572 mm) clearance above the sidewalk shall not extend into or occupy more than two- thirds the width of the sidewalk measured from the building.
3202.3.1.1 Support. Fixed awnings, marquees, signs or canopies shall be entirely supported from the building.
O. Section 3202.4 of the 2024 Edition of the International Building Code is hereby amended by deleting Section 3202.4 and substituting the following:
3202.4 Temporary encroachments. Where allowed by the local authority having jurisdiction, vestibules and storm enclosures shall not be erected for a period of time exceeding 90 days in any one year and shall not encroach more than 3 feet (914 mm) nor more than one-fourth of the width of the sidewalk beyond the street lot line. Temporary entrance awnings shall be erected with a minimum clearance of 8 feet (2438 mm) to the lowest portion of the hood or awning where supported on removable steel or other approved noncombustible support from the building.
P. Section D101.2 of the 2024 Edition of the International Building Code is hereby amended by deleting Section D101.2 and substituting the following:
D101.2 The Fire District shall include such territory or portion thereof as established by the official Fire Zone Map of the Metropolitan Government of Nashville and Davidson County, Tennessee.
(Ord. BL2025-898 § 1, 2025; Ord. BL2024-304 § 1, 2024; Ord. BL2024-182 § 2, 2024; Amdt. 1 to Ord. BL2023-1994 § 1, 2023; Ord. BL2023-1994 § 1, 2023; Ord. BL2020-458 § 1, 2020; Ord. BL2019-95 § 1, 2020; Amdt. 2 to Ord. BL2016-238 § 3, 2016; Ord. BL2016-238 §§ 3, 4, 2016; Ord. BL2015-1145 § 7, 2015; Amdt. 1 to Ord. BL2010-622 § 1; Ord. BL2010-622 § 1, 2010; Ord. BL2007-1390 § 7, 2007; Ord. BL2002-1142 § 14, 2002; Ord. BL2001-703 § 10, 2001; Ord. 98-1445 §§ 24—44, 1998; Ord. 96-562 §§ 3—8, 1996; Ord. 95-1542 § 2, 1995; Ord. 95-1487 §§ 4—19, 1995; Ord. 94-1113 §§ 3 and 4, 1994; Ord. 92-118 § 3, 1992)