14B-10-1021 Egress balconies.

The provisions of Section 1021 of IBC are adopted by reference with the following modification: 1. Revise Section 1021.4 to read: "1021.4 Location. Exterior egress balconies shall have a minimum fire separation distance of 10 feet (3048 mm) measured at right angles from the exterior edge of the egress balcony to: 1. The closest abutting property line. 2. The far side of a public way. 3. The exterior walls of other buildings on the same lot with openings that are not protected in accordance with Section 705 based on fire separation distance."