§ 21.49.110 — Electric service connection provisions
Seattle Municipal Code (Supp. No. 44: codified through Ordinance No. 127459, passed June 30, 2026) · Seattle Mun. Code § 21.49.110
Corpus is an independent public-information project, not the official City of Seattle website. Stable reference: corpuslaw.us/code/e9756f78-e26c-4d69-aac4-ebedd6ad8965
21.49.110 - Electric service connection provisions
A. Rule-making authority. The Department shall have the authority to adopt and enforce rules and regulations, consistent with this Chapter 21.49 and the provisions of Chapter 3.02, for the purpose of carrying out the provisions of this Chapter 21.49 governing availability of service and materials from the Department. Notwithstanding the repeal of Chapter 21.48, all existing rules and regulations adopted by the Department shall remain in effect until modified or revoked. B. Confirmation of meters 1. In buildings with multiple accounts, it shall be the responsibility of each customer (whether building owner, tenant, or agent) to confirm the number of meters installed at the customer's premises and check all meter numbers with the meter numbers on the electric service bill. It is the customer's responsibility to notify the Department in writing within 60 days of any discrepancy in meter numbers. The Department will assume no responsibility for retroactive adjustments due to incorrect meter number where such timely notice has not been received. 2. It shall be the responsibility of owners of buildings with multiple accounts, or their agents, to assure that all electric meters are connected to the appropriate apartment, housing unit, or business establishment. Apartments or dwelling unit addresses, including apartment numbers, shall not be changed or reordered without notifying the Department in writing at least 30 days prior to such change or reordering. In the event apartment or dwelling unit numbers or addresses are changed or reordered, the owner or the owner's agent shall notify the Department 30 days in advance of any such change. The Department may visit the site to verify such changes and confirm that each apartment or dwelling unit is connected to the proper meter. For such meter check by the Department, the building owner shall be billed the actual cost required to perform such meter check. C. Service entrance requirements. On initial installations or modifications to initial installations, the customer shall provide service entrance equipment which meets applicable Seattle and King County electrical codes and the Department's written rules and regulations. In the event a customer's electric service was installed before Seattle or King County enacted the current electrical code the customer may not be required by the electrical code to upgrade his/her service. It shall be the responsibility of the owner/customer to determine if changes to the electrical system are necessary to receive the safety benefits of the new or amended electrical codes and the National Electrical Code. It shall be a violation of this Chapter 21.49 to connect a building's electrical wiring to the Department's electrical system if the wiring of the building was not authorized by a proper City or county permit, does not meet the applicable existing electrical codes or was not inspected by the proper authority. D. Authority and responsibility for system design and construction. The design and construction of the Department's transmission and distribution system shall be within the sole discretion of the Department; such design and construction shall consider public and employee safety, system efficiency, system uniformity, and the economic impact of such design and construction on electric rates. In the event a customer wants any system (distribution) change for its own convenience or for aesthetics, the utility may at its sole discretion make such system change or modification, provided that the customer shall pay, in advance of construction, the estimated cost of time and materials and the final actual cost when the construction is completed. E. Prohibition of master metering 1. The Department shall not supply electricity for any new service to a duplex or multiple-dwelling building for the purpose of master metering the energy usage of the dwelling units, a central space heating system or HVAC system, or a central domestic water heating system. The Department shall not supply electricity for any larger service to an existing duplex or multiple-dwelling building for the purpose of master metering new central or individual space heating or HVAC systems. The existence of alternative laundry or dining arrangements for residents of multiple-dwelling buildings (such as central kitchens and dining rooms where residents can buy or eat their meals, or a central laundry), in addition to the availability of cooking and/or laundry facilities within the individual dwelling units, will not be considered grounds for an exemption from the prohibition of master metering. 2. This prohibition does not apply to multiple-dwelling buildings such as transitional housing, student dormitories and residences for religious orders, the elderly or the disabled, in which the residents do not live independently. 3. In situations with a mix of living accommodations where some residents live independently and some do not, those buildings or portions of buildings which provide non-transient independent dwelling units will not be eligible for master metering. 4. Accessory housing exception. A structure that only contains one principal dwelling unit and one accessory dwelling unit shall be exempt from the master metering provisions of this Chapter 21.49. 5. Other exceptions. Exemption from the master metering prohibition for residential dwelling situations not covered in the provisions of this Chapter 21.49 may be granted on a case-by-case basis by the Department. F. Efficiency standards 1. Pursuant to the Chapter 3.02, the Department shall adopt rules and regulations to promote conservation of the City's electric energy resources by the designation of end-use efficiency standards to limit energy waste from all new or enlarged electric service connections. The Department may also designate end-use efficiency standards to limit energy waste from conversions to electric space heat at existing electric service connections. For the purpose of this Section 21.49.110, "end-use" shall be defined as the final conversion of electric energy on the customer's premises into lighting, heating, cooling, and/or other mechanical processes. 2. The Department may require compliance with the rules and regulations as a condition for the supply or continued supply of electric service. 3. Pursuant to Chapter 3.02, the Department shall: a. Give notice of any public hearings held on proposed efficiency standards; b. Afford all interested persons an opportunity to present data, views or arguments in regard to proposed efficiency standards; c. Give appropriate consideration to economic values, along with any environmental, social, health, and safety factors affecting proposed efficiency standards. 4. The Department shall also apply the following specific criteria in developing, reviewing, and adopting all efficiency standards: a. Efficiency standards must be cost effective. An efficiency standard shall be considered cost effective if the life cycle costs of complying with the standard are below the incremental system costs of generating, transmitting, and distributing electricity from the least-cost alternative new source of supply. b. Efficiency standards must apply equitably to all customers in a customer class. c. Efficiency standards must be no more stringent than the City's requirements for new construction. 5. In adopting any new or amended efficiency standards after August 1, 1984, the Department may consider including the following requirements: a. A requirement that an electric energy analysis be performed; b. A requirement that the customer implement the electric energy analysis recommendations; c. A requirement that the size of service be limited to that required to serve the intended use of electricity in order to prevent oversizing the service; d. A requirement that a customer provide the Department with advance notice of any request for a new or enlarged service connection. 6. In the development of each efficiency standard the Department shall solicit technical assistance from the customer class affected by the standard. In addition, the Department shall periodically review and evaluate all efficiency standards designated pursuant to this chapter and shall revise them as necessary to reflect the changing needs of the Department's generation, transmission, and distribution systems. G. Protective devices 1. The Department may require customers to provide on their premises, at their own expense, additional protective devices deemed necessary by the Department to protect the Department's property or personnel, or the property or personnel of the Department's other customers. However, failure to require such protective devices does not relieve the customer of its responsibility to provide the necessary protective devices to protect itself, its property and/or equipment from electrical transients, surges and/or loss of power. 2. It is the responsibility of customers using sensitive electronic equipment, computers, and computer peripheral equipment to provide, at their own expense, all protective devices necessary to protect such equipment against electromagnetic fields, natural and switching transients, power surges, planned power outages, emergency power outages, and any other occurrence which occurs on the Department's electrical system that is not within the control of the Department or is due to the natural mechanical failure of any of the equipment utilized to support and operate the Department's electrical system. It is also the customer's responsibility to provide the necessary emergency backup electrical system sufficient to protect the customer's sensitive electronic equipment and provide emergency electrical power as necessary to operate essential personal, business and medical equipment. H. Three phase motors: protective devices. Customers shall have the responsibility to provide suitable devices adequate to protect their three phase motors and other equipment against reversal of phase rotation and single phasing. I. Devices to control quality of energy. Where the customer's use of electrical equipment results in an interference with the quality of the customer's own service or that of neighboring customers, or where the customer requires voltage control within unusually close limits, the Department may require the customer to provide at the customer's own expense such special or additional equipment as is required. This may apply to cases of extreme unbalance of single and three phase loads. Customer loads which cause voltage fluctuation, harmonic current distortion, or harmonic voltage distortion shall not exceed the values given in "IEEE Recommended Practices and Requirements for Harmonic Control in Electric Power Systems, IEEE-519," latest revision. J. License requirements. It shall be unlawful for any person other than a duly authorized Department employee or agent of the Department to make an electrical connection between the Department's electrical system and any customer's wiring. With the written approval of the Department, a customer may contract with a qualified electrical contractor licensed under chapter 19.28 RCW to install any material or equipment in lieu of having Department personnel perform the installation. The qualified electrical contractor shall be solely responsible for any damages resulting from the installation of any temporary service, permanent service, or expanded service and the Department shall be immune from any tortious conduct actions as to that installation. K. Authorized service connections 1. No customer shall connect their service with that of any other customer, or in any way supply any other person or premises with electricity through their service, except as approved by the Department after the filing of a written application with the Department for the connection and receipt of a permit from the Department for connection. 2. Master-metered services approved prior to October 5, 1978 are exempt. 3. New or enlarged services to a duplex or multiple-dwelling building shall have common areas and common equipment supplied through a separate house meter. L. Hazardous wiring. The Department may refuse to connect the applicant's service conductors to the Department's electrical system or may disconnect an existing service if in the Department's judgment the applicant's wiring or electrical equipment is hazardous to life or property, or the Department's written rules and regulations have not been followed. M. Maintenance of safe wiring. Customers shall at all times keep their wiring and electrical equipment in such condition that the wiring and equipment can be used without causing damage to the Department, its property, or personnel. The Department shall have the authority at any time to disconnect its electrical system from any wiring or electrical equipment that is defective or dangerous and refuse to reconnect its electrical system until the defective or dangerous wiring or electrical equipment is properly repaired or restored. N. Access to meters 1. Any duly authorized Department employee shall have free and safe access at any reasonable time to any and all premises furnished with electricity by the Department, for the purpose of reading, inspecting, repairing, installing, or removing meters, electrical devices, or wiring of the Department, for the connection or disconnection of service, or for any other reasonable purpose connected with the performance of the contract for the provision of electric service. The owner, tenant, or person in control of the premises shall restrain and control all dogs or animals of any kind that limit or appear to limit safe access to the premises for any of the purposes cited above. It shall be the responsibility of the owner, its agent, or the tenant to remove all safety hazards that might in any way harm or injure authorized City employees performing their duties. Such safety hazards shall include, but not be limited to, booby traps of any kind, construction hazards, sharp or falling objects or debris that may cause injury. The determination of whether a condition is safe will be in the sole discretion of the City employee seeking entry to the premises. 2. For the Department's systems in underground network areas, twenty-four (24) hour personnel access shall be provided to all vaults and switchgear rooms on customer property. Upon request, the customer shall correct any condition that limits or restricts free and safe access to the Department's meters or service. Failure of the customer to comply within a reasonable time specified shall subject the customer to disconnection of service. 3. No customer shall convert any room or other building area containing electrical meters, or other devices or wiring of the department, to a dwelling unit or other type of living quarters. 4. If a room or other building area containing electrical meters or other department equipment is partitioned, the area containing such equipment shall have separate access to common areas or to the outside. All other adopted requirements and regulations for access, clearance, locations, etc., shall apply. 5. Upon request the customer shall separate electrical meters or other department equipment from living quarters in accordance with the provisions above. Failure of the customer to comply within a reasonable time specified shall subject the customer to disconnection of service. O. Meter seals. The Department may install sealable locking devices on certain enclosures containing unmetered conductors, including but not limited to meter sockets, meter enclosures, current transformer enclosures, test switch enclosures, wire troughs, bus gutters, and terminal boxes. P. Meter tampering protection. When current has been diverted around the Department's metering equipment or when the Department's metering equipment has been tampered with to adversely affect metering registration, the Department may require the customer or property owner at his/her expense to repair, relocate, or replace his/her service entrance equipment in a manner determined by the Department to prevent future incidents of current diversion. Q. Customers' responsibility. Notwithstanding any other provisions of any other code or ordinance: 1. It is the responsibility of customers to protect themselves, life, and property from the use, misuse, and/or availability of electrical current on their premises and from the consequences of the use, misuse, and/or availability of electrical current on their premises. 2. It is the responsibility of customers to provide, install, use, inspect, and maintain suitable protection and protective devices to protect themselves, life, and property from any defect, failure, malfunction, and/or electrical fault in or originating in any electrical wiring, current-consuming devices, or other equipment which they may own, operate, install, or maintain; and to protect themselves, life, and property from the consequences of any defect, failure, malfunction, and/or electrical fault in or originating in any electrical wiring, current-consuming devices, or other equipment which they may own, operate, install, or maintain, including protection from surge voltages generated within their premises and generated by lightning, switching, and arcing on the Department's system to the full range of parameters described in "IEEE Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits, C62.41-1991," or latest revision. Customers may consult with Department personnel, but such consultation shall not absolve customers from any of the responsibilities in this Chapter 21.49, nor shall such consultation be relied upon as providing any substitute for professional advice from the customer's own engineers or contractors. It is the responsibility of customers to maintain their electrical systems and to ensure that their electrical service equipment meets all current electrical codes and standards. The Department's responsibility ends and the customer's responsibilities begin at the weatherhead or other point of service as specified by the most recent version of Requirements for Electric Service Connection. The customer's service includes, but is not limited to, electrical service panels and entrance equipment (including meter sockets and enclosures), and ducts, vaults, and handholes on the customer's side of the point of service connection. In the case of failure of or damage to direct buried service conductor, the customer is responsible for digging a trench to facilitate repair of the conductor. R. Customer's liability. Nothing in this Chapter 21.49 shall be construed as placing upon the Department any responsibility for the condition, maintenance, or safety of customers' electrical wiring or current-consuming devices or other equipment; and the Department shall not be responsible for any loss or damage resulting from defects, failures, malfunctions, or electrical faults in or originating in any electrical wiring, current-consuming devices, or other equipment which customers may own or operate, install or maintain. The Department shall not be responsible for damage to persons or property arising from the use of electric service on the premises of the customer. S. Notification of added load. In order to prevent damage to the Department's equipment and impairment of its service, customers shall give the Department notice before making any additions to their connected load so that the Department, at its option, may provide the facilities which may be necessary for furnishing the increased service. The customer shall be liable for any damages to the Department that may occur and for any additional charges that may accrue as a result of the failure to so notify the Department. T. Installation charges. Any applicant or customer receiving a new or an enlarged service installation or converting an existing service from an overhead connection to an underground connection shall be charged the material and labor costs incurred by the Department in making the installation less the material and labor costs of transformers and associated network protectors supplied by the Department. The Department shall have the authority to establish standard installation charges representing the average material and labor costs for customers who receive basic service installations which do not require a vault as specified in the Department's Requirements for Electric Service Connection manual. Such standard charges shall be developed pursuant to the provisions of Chapter 3.02. All applicant(s) or customer(s) receiving the conversion of an existing overhead electrical distribution system to an underground system shall: 1. Reimburse the utility in full for all materials and labor costs in excess of the salvage value of the existing overhead system and conversion costs, if any, from 4 to 26 kV; 2. Reimburse the utility in full for material and labor costs, if any, to underground and/or replace/install streetlights. Installation charges are not rates for electrical service and reflect only costs incurred by the Department for new and expanded services. U. Losses from interruptions of service 1. The Department shall not be liable for any loss, injury, or damage resulting from the interruption, fluctuation, restoration, or reduction of electric service from any cause beyond the control of the Department, including, but not limited to, fire, flood, drought, winds, acts of elements, court orders, interruptions or riots, generation failures, lack of sufficient generation capacity, breakdowns or damage to facilities of the Department or of third parties, acts of God or public enemy, strikes or other labor disputes, civil, military, or governmental authority, electrical disturbances originating on or transmitted through the electrical systems with which the Department system is interconnected, and acts or omissions of third parties. 2. In the event of electric service interruption, fluctuation, or reduction resulting from damage to or failure of Department equipment or facilities, the Department has the sole authority to determine the order of repairs. In making the determination of the order of repairs, the Department may consider, but is not bound to, the following order of repair and energization: substations, feeders to police and hospital facilities, and feeders to residential and industrial facilities. 3. Moreover, the Department shall not be liable for any such loss resulting from repair, maintenance, improvement, renewal, or replacement work on the Department's electrical system, which work, in the sole judgment of the Department, is necessary or prudent. To the extent practical, work shall be done at such times as will minimize inconvenience to the customer and the customer shall be given notice of such work in accordance with the rules and policies of the Department. Further, the Department's liability shall be limited for failure of generation and distribution, inadequacy of energy supply, implementation of emergency plans, or temporary disconnection for repairs and maintenance or for failure to pay for service rendered. V. Emergencies. During an emergency declared by appropriate civil authority, the Department shall have the authority to curtail electric service to any customer. The Department shall have the authority to restrict the use of loads and/or services during periods of emergency when the Department, in its sole judgment, determines that the continued use of the loads would jeopardize the Department's generation, transmission, or distribution system. Operation of the Department's automatic relay/breaker system is sufficient cause to terminate service. The Department shall prioritize its repair responses during declared emergencies or during system outages caused by weather conditions. In the event of a declared emergency, the Department shall prioritize the restoration of its electrical system, first by responses to directions or orders of the Mayor and Emergency Control Center, and next by restoration of power to the Department's electrical system as the Department's electrical system judgment dictates. W. No express or implied warranty. The Department provides no express or implied warranties involving the electrical service provided by the Department, including the design and construction of the Department's electrical system, or its transmission and distribution systems. X. Amp fee for new or enlarged services. The Department shall charge all developers, customers, and contractors who install new or enlarged electrical services a fee per panel ampere (commonly abbreviated as "amp"), which is required to be paid before the Department will energize the service. The amp fee is established in accordance with the Administrative Code process and set out in Department Policy and Procedures 500 P III-417, Schedule 100, and 500 P III-422, Schedule 100. The fee shall apply to all permanent installations.
(Ord. 127376, § 7, 2025; Ord. 125171, § 13, 2016; Ord. 124578, § 1, 2014; Ord. 123604, § 2, 2011; Ord. 122523, § 7, 2007; Ord. 122282, §§ 16, 17, 2006; Ord. 119747, § 1, 1999; Ord. 118475, § 14, 1997; Ord. 117490, § 16, 1995; Ord. 116619, § 14, 1993; Ord. 114835, § 9, 1989; Ord. 114459, § 13, 1989; Ord. 112738, § 9, 1986; Ord. 112441, § 8, 1985; Ord. 111615, 1984; Ord. 110919, § 3, 1982; Ord. 110733, 1982.)
Ask a question about Seattle law
Corpus searches the Seattle sections it holds and shows the ones that match, with their citations. Free, no sign-in.