Sec. 13-196. - Fire protection required for self-service fueling stations.
Pursuant to authority conferred in the Code of Virginia, self-service fueling stations must operate either with an attendant present, or operate only while meeting the following minimum requirements: (1) Listed dispensing devices shall be used. Coin and currency-type devices shall not be permitted. (2) Emergency controls specified in the Virginia Statewide Fire Prevention Code shall be installed at a location as approved in writing by the Fire Marshal, but in any event such controls shall be installed more than 20 feet and less than 100 feet from the dispensers. Additional emergency controls shall be installed on each group of dispensers or the outdoor equipment used to control the dispensers. Emergency controls shall shut off power to all dispensing devices at the station. Controls shall be manually reset only in a manner approved in writing by the Fire Marshal. (3) Operating instructions shall be conspicuously posted in the dispensing area, and shall include location of emergency controls, and a requirement that the user must stay outside of the user's vehicle, in view of the fueling nozzle during dispensing. (4) In addition to those warning signs specified in the Automotive and Marine Service Station Code, emergency instructions shall be conspicuously posted in the dispensing area incorporating the following or equivalent wording: a. Emergency Instructions. b. In case of fire or spill: 1. Use emergency stop button. 2. Report accidents by calling (specify local fire number) on phone. Report location. (5) A listed, automatic-closing type hose nozzle valve without latch-open device shall be provided. The system shall include listed equipment with a feature that causes or requires the closing of the hose nozzle valve before the product flow can be resumed or before the hose nozzle valve can be replaced in its normal position in the dispenser. (6) A telephone or other clearly identified means to notify the Department of Fire and Emergency Services, as approved in writing by the Fire Marshal, shall be provided on the site in a location approved in writing by the Fire Marshal. (7) The facility shall not operate without having in place and operable the following systems as approved in writing by the Fire Marshal: a. Fixed fire suppression system. b. Automatic fire detection system. c. Transmission of alarms to the Department of Fire and Emergency Services. d. System to limit gallonage delivered per vehicle. (8) Notwithstanding the foregoing, any card or key operated self-service fueling station that is accessible only by employees of a single, common owner or operator may operate without an attendant and without meeting the minimum requirements set forth in this section if and only if all other legal requirements of the Virginia Statewide Fire Prevention Code are met. (9) The requirements set forth in this section are in addition to and do not limit the application of other legal requirements to fueling stations or the Fire Marshal's discretionary authority.
(Code 2004, § 46.1-59; Code 2015, § 13-196; Code 2020, § 13-196; Ord. No. 2006-150-165, § 3, 6-12-2006)
Ask a question about Richmond law
Corpus searches the Richmond sections it holds and shows the ones that match, with their citations. Free, no sign-in.