Omaha Municipal Code § 49-1400 Generally.
Sec. 49-1400. - Generally.
All plumbing fixtures shall be separately trapped by a water seal P-trap, placed as close to the fixture outlet as possible.
Exceptions:
(a) A two or three-compartment sink may be served by one trap when one compartment is not more than six inches deeper than the other and the waste outlets are no more than 30 inches apart.
(b) Where it is not practical to install a return vent at a drinking fountain, lavatory, or sink placed away from the sidewalls, a properly vented trap may be placed below the finished floor in a readily accessible location. (See Figure 49-1400(b).)
(c) Interceptors, rainwater leaders, and special wastes shall be trapped as otherwise provided for in this code.
(Ord. No. 40524, § 1, 10-20-15)