§ 16-91 — Environmental air ducts; requirements for installation or replacement
Code of Ordinances of the City of Pasadena, Texas (Supp. No. 33, Update 2: codified through Ordinance No. 2026-143, enacted September 1, 2026) · Pasadena City Code § 16-91
Corpus is an independent public-information project, not the official City of Pasadena website. Stable reference: corpuslaw.us/code/f82a1dea-72f6-4470-9ef6-6d5b919e48c9
Sec. 16-91. - Environmental air ducts; requirements for installation or replacement.
(a) Flex duct or duct board shall be a minimum of R-8. All duct insulation shall meet R-8 minimum requirement, unless required by the energy code to be more restrictive. (b) All register boxes and bath fans shall be supported on a minimum of two (2) sides, and sealed. (c) Residential bathrooms with open window area of at least three (3) square feet shall not require bath exhaust fans. If exhaust fans are required they shall be vented to outside. (d) Domestic ranges shall have a hood with exhaust vented to outside and made of smooth sheet metal, connected by listed fittings, and with a back draft damper. (e) Clothes dryer exhaust ducts shall be smooth sheet metal with no screws. Four-inch duct shall not run over twenty-five (25) feet in total length with two (2) elbows, additional elbows will deduct five (5) feet from total length for each elbow. A run may be extended to forty (40) feet by increasing the duct to five (5) inches with a listed increaser. The elbows will apply the same as for the four-inch exhaust duct. All dryer exhaust ducts, not vented thru the wall, shall have lint traps installed below the flex connector at the wall. Lint traps shall be made with a four-inch metal "T" and a four-inch metal ninety (90), with an end cap on the lint trap end. When vents for dryers or domestic ranges are vented thru a roof jack, a sheet metal escutcheon shall be installed to seal off the vent at the roof jack. No tape will be allowed to seal off vents in roof jack. Gas clothes dryers in enclosed rooms shall have a minimum of one (1) square inch per thousand BTU's of make-up air. An exhaust fan, vented to the outside of the house or building, is required unless the room has an operable window. (f) Fresh air duct shall be smooth sheet metal duct extended to outside of building with one-fourth-inch bird screen at outside termination, and filtered. (g) Combustion air may be taken from an attic area, if attic is communicable with outside air, otherwise it must be taken from outside of building. Combustion air duct shall be smooth sheet metal, and of sufficient dimensions to allow one (1) square inch per three thousand (3,000) BTU's, or in enclosed room providing fifty (50) cubic feet per thousand (1,000) BTU's of all gas fired equipment in the room.
(Ord. No. 17-009, § 1(Exh. A), 1-17-17)
Ask a question about Pasadena law
Corpus searches the Pasadena sections it holds and shows the ones that match, with their citations. Free, no sign-in.