Sec. 16-89. - Evaporator coils: Requirements for installation.
(a) All evaporator cooling coils, or air conditioning units with cooling coils placed above a finished ceiling, closet, or any location that may cause damage, shall have a secondary drain run to a readily observable location. All secondary drain pans shall require a float switch. Package units shall require a float switch in the main drain pan. All float switches shall be listed by an approved testing laboratory. All new installations shall have emergency drains. (b) Horizontal evaporator coils and plenums shall be supported on both sides with one (1) inch metal straps. Where straps are attached to over-head rafters or other wooden supports; nails or screws used shall be one (1) inch in length. No perforated straps shall be used. (c) A minimum eight by eight (8×8) inch listed inspection door shall be installed in the transition for horizontal evaporator coils. (d) When replacing evaporator coils, condensate drains will be brought up to current code standards.
(Ord. No. 17-009, § 1(Exh. A), 1-17-17)