Sec. 5-8. - International Residential Code adopted.
(a) [Adopted.] The International Residential Code for One- and Two-Family Dwellings, 2012 edition, including Appendix Chapter "J", a copy of which has been reviewed by the mayor and board of aldermen, be and is hereby adopted.
(b) [Amendments.] The following sections are hereby revised:
Section R101.1. Insert: City of Batesville.
Section R105.5. Expiration. Every permit, except demolition permits, issued shall become invalid unless the work authorized by such permit is commenced within 180 days after its issuance, or if the work authorized by such permit is suspended or abandoned, for a period of 180 days after the time the work is commenced. Demolition permits shall expire in 90 days from the date of issuance. The building official is authorized to grant, in writing, one or more extensions of time, for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated.
Table R301.2. (1) Insert: GROUND SNOW LOAD - 10; WIND DESIGN - Speed 90 mph; Topographic effects - No; SEISMIC DESIGN CATEGORY - C; SUBJECT TO DAMAGE FROM - Weathering - M; Frost line depth - 12"; Termite - VH; WINTER DESIGN TEMP - 21; ICE BARRIER UNDERLAYMENT REQUIRED - No; FLOOD HAZARDS - Jan. 29, 1990; Panel #280126 0005C dated Sept. 15, 1989; Panel #280125 0120B dated June 4, 1980; LOMR - dated Sept. 19, 1994; LOMR - dated March 3, 2006; AIR FREEZING INDEX - 169; MEAN ANNUAL TEMP - 61.2.
Section R302.2. Townhouses - Exception: A common two-hour fire-resistance-rated wall assemble tested in accordance with ASTME 119 or UL 263 is permitted for townhouses if such walls do not contain plumbing or mechanical equipment, ducts or vents in the cavity of the common wall. This rating may be reduced to one-hour when the townhouses on both sides of such wall are equipped throughout with an automatic sprinkler installed in accordance with NFPA 13D. The wall shall be rated for fire exposure from both sides and shall extend to and be tight against exterior walls and the underside of the roof sheathing. Electrical installations shall be installed in accordance with Chapters 34 through 43. Penetrations of electrical outlet boxes shall be in accordance with Section R302.4.
Section R302.2.4. Structural Independence - Exceptions: 5. Townhouses separated by a common two-hour fire-resistance-rated wall as provided in Section R302.2.
Section R302.5.1. Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Non-fire-rated doors shall be allowed between the garage and residence.
Section R313.1. Townhouse automatic fire sprinkler systems. An automatic residential fire sprinkler system shall be optional and not mandatory in townhouses.
Section R313.2. One- and two-family dwellings automatic fire systems. An automatic residential fire sprinkler system shall be optional and not mandatory in one- and two-family dwellings.
Section E3902.12 Arc-fault circuit-interrupter protection. Branch circuits that supply 120-volt, single-phase, 15- and 20-ampere outlets in bedrooms shall be protected by a combination type arc-fault circuit interrupter installed to provide protection of the branch circuit.
Section P2603.5.1. Insert: "6 inches" in first blank; Insert: "12 inches" in second blank.
(Ord. No. 83-217, § 1, 12-2-80; Ord. No. 03-11-644, § 1, 11-18-03; Ord. No. 2008-03-704, §§ 1, 2, 3-18-08; Ord. No. 2009-01-719, § 1, 1-7-09; Ord. No. 2009-12-731, § 1, 12-15-09; Ord. No. 2010-12-750, § 1, 12-21-10; Ord. No. 2011-02-753, 2-1-11; Ord. No. 2014-07-798, §§ 1, 2, 7-15-14, eff. 10-1-14; Ord. No. 2014-08-810, §§ 1, 2, 8-19-14, eff. 10-1-14; Ord. No. 2020-09-880, § 1, 9-15-20)