§ 18.68.221 — Standard No. 24-41, tests of anchors in unreinforced masonry walls

Long Beach Municipal Code (Supp. No. 53, Update 1: codified through Ordinance No. ORD-26-0027, enacted October 13, 2026) · Long Beach Municipal Code § 18.68.221

Corpus is an independent public-information project, not the official City of Long Beach website. Stable reference: corpuslaw.us/code/fe6464ff-c063-4c7f-b54c-695901fa663c

18.68.221 - Standard No. 24-41, tests of anchors in unreinforced masonry walls.

A. Existing Anchors. The test apparatus shall be supported on the masonry wall at a minimum distance of the wall thickness from the anchor tested. Existing wall anchors shall be given a preload of three hundred (300) pounds prior to establishing a datum for recording elongation. The tension test load reported shall be recorded at one-eighth (⅛) inch relative movement of the anchor and the adjacent masonry surface. Results of all tests shall be reported. The report shall include the test results as related to the wall thickness and joist orientation. [image omitted; see the official code] TABLE NO. A-23-A HORIZONTAL FORCE FACTOR C p CONFIGURATION OF MATERIALS | C p Roofs with straight or diagonal sheathing and roofing applied directly to the sheathing, or floors with straight tongue and groove sheathing. | 0.5 Diagrams with double or multiple layers of Boards with edges offset and blocked plywood systems. | 0.74 TABLE NO. A-23-B ALLOWABLE VALUE OF HEIGHT-THICKNESS RATIO OF UNREINFORCED MASONRY WALLS Wall Types | Buildings with Crosswalls 1 | All Other Buildings Walls of one-story buildings | 16 2,3 | 13 First-story wall of multi-story building | 16 | 15 Walls in top story of multi-story buildings | 14 2,3 | 9 All other walls | 16 | 13 TABLE NO. A-23-C ALLOWABLE VALUES FOR EXISTING MATERIALS EXISTING MATERIALS OR CONFIGURATIONS OF MATERIALS 1 | ALLOWABLE VALUES 1. HORIZONTAL DIAPHRAGMS 4 a. Roofs with straight sheathing and roofing applied directly to the sheathing. | 100 lbs. per foot for seismic shear b. Roofs with diagonal sheathing and roofing applied directly to the sheathing. | 250 lbs. per foot for seismic shear c. Floors with straight tongue-and-groove sheathing. | 100 lbs. per foot for seismic shear d. Floors with straight sheathing and finished wood flooring with Board edges offset or perpendicular | 500 lbs. per foot for seismic shear e. Floors with diagonal sheathing and finished wood flooring. | 600 lbs. per foot for seismic shear 2. CROSSWALLS 2,4 a. Plaster on wood or metal lath | Per side: 200 lbs. per foot for seismic shear b. Plaster on gypsum lath | 175 lbs. per foot for seismic shear c. Gypsum wall Board, unblocked edges | 75 lbs. per foot for seismic shear d. Gypsum wall Board, blocked edges | 125 lbs. per foot for seismic shear 3. EXISTING FOOTINGS, WOOD FRAMING, STRUCTURAL STEEL, AND REINFORCED CONCRETE a. Plain concrete footings | F'c = 1500 psi unless otherwise shown by tests 3 b. Douglas fir wood | Allowable stress same as No. 1 D.F. 3 c. Reinforcing steel | f t = 18,000 lbs. per square inch maximum. 3 d. Structural steel | f t = 20,000 lbs. per square inch maximum. 3 TABLE A-23-E β Factors SYSTEM | β A. URM Bearing Wall Building | 1.0 B. Ordinary Steel Moment Frame 1. Without infill (after removal of infill) | .065 (1) 2. Clay tile infill | (3) 3. Unreinforced masonry or concrete infill | 0.65 (2) 4. Reinforced masonry or concrete infill | 0.80 (2) C. Ordinary Concrete Moment Frame 1. Without infill (after removal of infill) | 0.65 (1) 2. Clay tile infill | (3) 3. Unreinforced masonry or concrete infill | 0.65 (2) 4. Reinforced masonry or concrete infill | 0.80 (2) TABLE A-23-F φOCCUPANCY LOAD FACTOR OCCUPANT LOAD * | φ 100 or more | 1.25 Less than 100 | 1.0 B. Combined shear and tension bolts. Combined shear and tension bolts embedded in unreinforced masonry walls shall be tested using a torque calibrated wrench to the following minimum torques: ½-inch-diameter bolts — 40 foot lbs. ⅝-inch-diameter bolts — 50 foot lbs. ¾-inch-diameter bolts — 60 foot lbs. All nuts shall be installed over malleable iron or plate washers when bearing on wood and heavy cut washers when bearing on steel.

(ORD-25-0019 § 1(Exh. A), 2025; ORD-22-0033 § 1(Exh. A), 2022; ORD-19-0031 § 1(Exh. A), 2019; ORD-16-0026 § 1(Exh. A), 2016)

Ask a question about Long Beach law

Corpus searches the Long Beach sections it holds and shows the ones that match, with their citations. Free, no sign-in.