Sec. 102-377. - Gravity grease interceptor cleaning and maintenance requirements.

(a) Partial pump of interceptor contents or on-site pump and treatment of interceptor contents will not be allowed due to reintroduction of fats, oils, and grease to the interceptor. In no way shall the pumped material be returned to any private or public portion of the sanitary sewer collection system. All grease waste haulers and procedures for pumping grease interceptors shall comply with the City of Dothan, part II, Code of Ordinances, chapter 102—utilities, article IV—sewer, section 102-300—commercial wastewater disposal service. (b) Gravity grease interceptors must be pumped-in-full (total pump of all contents) when the total accumulations of surface FOG (including floating solids) and settled solids reaches 25 percent of the grease interceptor's inlet liquid depth. This criterion is referred to as the "25 percent rule." At no time shall the cleaning frequency exceed 90 days unless approved in writing by the city. Failure to meet these requirements shall result in enforcement action. Approval will be granted on a case by case situation with submittal by the FSE documenting proof that a reduced cleaning frequency will meet the requirements of this FOG ordinance. Some FSEs may need to consider a more frequent pumping schedule to meet this requirement. A city approved manifest of gravity grease interceptor cleaning/maintenance, and an FSE gravity grease interceptor self-monitoring checklist shall be maintained onsite at the FSE and provided to the city upon request. These documents need to be provided to the city for review before consideration for approval can be granted for a cleaning frequency to exceed 90 days. (c) The gravity grease interceptor's influent tee and effluent tee will be inspected during cleaning and maintenance and the condition noted by the grease waste hauler's company or individual conducting the maintenance. Influent and effluent tees that are loose, defective, or not attached must be repaired or replaced immediately. Grease waste haulers or individuals conducting any maintenance or pumping will use caution to not damage or dislodge tees, or cause other grease interceptor component damage. Any repairs to the grease interceptor shall be documented and kept on file at the FSE. (d) All gravity grease interceptors must have access manholes over the influent tee and effluent tee for inspection and ease of cleaning/maintenance. Access manholes will be provided for all separate compartments of interceptors for complete cleaning (i.e. interceptor with two main baffles or three compartments will have access manholes at each compartment). The manholes are to be readily accessible for inspection by the city. (e) Gravity grease interceptor waste must be hauled offsite and disposed of, processed, or recycled at an approved location in accordance with applicable laws. All disposal of grease interceptor waste must meet the requirements of City of Dothan, part II, Code of Ordinances, chapter 102—utilities, article IV—sewer, section 102-300—commercial wastewater disposal service. City approved manifests must be used and properly completed. (f) Gravity grease interceptors must be "certified" annually by a city certified grease waste hauler or city certified plumber. A gravity grease interceptor certification (form a) must be properly completed and submitted to the city annually. (g) The city may mandate the FSE to require the grease waste hauler to contact the city's FOG program by telephone at least 24 hours prior to any cleaning, pumping, maintenance, inspection, or certification of the grease interceptor. The city reserves the right to be present to inspect all maintenance. (h) Responsibility. Maintaining the gravity grease interceptor(s), including complete pumping of contents at the required frequency and insuring proper components are installed, is the responsibility of the user/owner. Commercial property owners shall ensure that lease agreements identify the responsible party for proper maintenance to control wastewater discharged from their property.

(Ord. No. 2015-366, § 1, 12-15-15)

Ask a question about Dothan law

Corpus searches the Dothan sections it holds and shows the ones that match, with their citations. Free, no sign-in.