§ 8-560 — Technical updates
The Little Rock City Code, Revised 1988 (Supp. No. 83: codified through Ordinance No. 22,703, enacted December 16, 2025) · Little Rock City Code § 8-560
Corpus is an independent public-information project, not the official City of Little Rock website. Stable reference: corpuslaw.us/code/737f1b4d-1294-419b-a92a-64ac33b580b6
Sec. 8-560. - Technical updates.
(a) Flex duct shall be allowed only on branch lines. (b) Flex duct shall be no longer than six (6) feet in length in commercial and ten (10) feet in length in residential installations. (c) Mechanical approved fittings are required for all turns and take-offs in flex duct installation. (d) Flex duct shall not be allowed in crawl spaces in residential or commercial occupancies. (e) Fiber duct (duct board) shall not be allowed. (f) Mechanical contractor shall submit a heat load with each permit application.
(Ord. No. 18,553, § 5, 9-4-01)
Ask a question about Little Rock law
Corpus searches the Little Rock sections it holds and shows the ones that match, with their citations. Free, no sign-in.
