§ 15.32.100 — Section 903.2.—Amended
Municipal Code of the City of Daly City, California (Codified through Ordinance No. 1492, passed June 8, 2026 (Supp. No. 39)) · Daly City Municipal Code § 15.32.100
Corpus is an independent public-information project, not the official City of Daly City website. Stable reference: corpuslaw.us/code/816f9db3-980a-4203-a35d-97a45163534c
15.32.100 - Section 903.2.—Amended.
Section 903.2 of this code is deleted in its entirety and is replaced with the following: Section 903.2 Where Required. A fire extinguishing system shall be installed in all occupancies and locations as set forth in this section. A. All Occupancies. All occupancies shall be protected throughout by an automatic fire sprinkler system installed in accordance with NFPA 13. Exceptions: Detached garages less than 400 square feet in size. Detached carports and greenhouses. Sheds and auxiliary structures under 200 square feet in size and not used for human habitation. B. Existing Occupancies. When an existing building undergoes any alteration, renovation, addition, or repair which exceeds 50% of the building's original gross area within any five (5) year period, the entire building shall be protected by an automatic fire sprinkler system. Gross area shall be the area included within surrounding exterior walls. Exceptions: Work involving exterior surfaces only, such as the replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck. C. For purposes of this section, an addition, alteration or repair is defined as any change to a building that requires a permit other than only a mechanical, electrical or plumbing permit. D. Other Areas. An automatic fire sprinkler system shall be installed in all garbage compartments, rubbish and linen chutes, linen rooms, incinerator compartments, dumb waiter shafts, and storage rooms when located in all occupancies except Group R, Division 3. An accessible indicating shut off valve shall be installed. E. Condominium Conversions. An automatic fire sprinkler system shall be installed for all condominium conversions.
(Ord. No. 1484, § 2(Exh. L), 11-24-2025)
Ask a question about Daly City law
Corpus searches the Daly City sections it holds and shows the ones that match, with their citations. Free, no sign-in.