§ 15.32.110 — Automatic sprinkler systems—Added

Municipal Code of the City of Daly City, California (Codified through Ordinance No. 1492, passed June 8, 2026 (Supp. No. 39)) · Daly City Municipal Code § 15.32.110

Corpus is an independent public-information project, not the official City of Daly City website. Stable reference: corpuslaw.us/code/d75c1714-a447-4f3b-b160-2145fd0377d4

15.32.110 - Automatic sprinkler systems—Added.

Add Sections 903.2.22. Purpose: To establish requirements for sprinkler protection of car stackers not specifically addressed in NFPA 13. Parking garage areas containing car stackers shall be protected by an automatic wet-pipe sprinkler system designed to Extra Hazard Group 2. In addition, non-extended coverage standard sidewall sprinklers listed for Ordinary Hazard shall be provided under each parking level, including the bottom level if the stacker is provided with a pit. Each sidewall sprinkler shall cover an area of 80 sq. ft. or less. The area of application may be reduced from the required 2500 sq. ft. to as low as 1500 sq. ft. if: 1. 1-hour fire rated walls are provided to separate the car stacker areas from the standard parking stalls, 2. The car stacker areas are divided up into 1500 sq. ft. areas via 1-hour fire rated walls, and 3. One-hour fire rated walls are provided to separate the car stacker areas from any other areas in the garage. One-hour fired rated walls are not required in the driveway areas. For the hydraulic calculation, flow from all sprinklers, upright or pendent sprinklers at ceiling and all sidewall sprinklers at all levels, located in the area of application shall be included in the calculation.

(Ord. No. 1484, § 2(Exh. L), 11-24-2025)

Ask a question about Daly City law

Corpus searches the Daly City sections it holds and shows the ones that match, with their citations. Free, no sign-in.