§ 13.08.030 — Cross-connection protection requirements
Municipal Code of the City of El Monte, California (Codified through Ordinance No. 3055, passed June 11, 2025. (Supp. No. 36, Update 1)) · El Monte Municipal Code § 13.08.030
Corpus is an independent public-information project, not the official City of El Monte website. Stable reference: corpuslaw.us/code/729c32ed-e24b-4d48-8027-67f4d615f281
13.08.030 - Cross-connection protection requirements.
A. General Provisions. 1. Unprotected cross-connections with the public water system of the Water Company are prohibited. 2. Whenever backflow protection has been found necessary, the Water Company will require the water user to install an approved backflow prevention device by and at his/her expense for continued service or before a new service will be granted. 3. Wherever backflow protection has been found necessary on a water supply line entering a water user's premises, then any and all water supply lines from the Water Company entering such premises, buildings, or structures shall be protected by an approved backflow prevention device. This type of device to be installed will be in accordance with the requirements of this resolution. B. Where Protection is Required. 1. Each service connection from the Water Company public water system for supplying water to premises having an auxiliary water supply shall be protected against backflow of water from the premises into the public water system unless the auxiliary water supply is accepted as an additional source by the Water Company, and is approved by the Health Agency. 2. Each service connection from the Water Company public water system for supplying water to any premises on which any substance is handled in such fashion as may allow its entry into the public water system shall be protected against backflow of the water from the premises into the public water system. This shall include the handling of process waters and waters originating from the Water Company public water system which have been subjected to deterioration in sanitary quality. 3. Backflow prevention devices shall be installed on the service connection to any premises having (a) internal cross-connections that cannot be permanently corrected and controlled to the satisfaction of the Health Agency and the Water Company, or (b) intricate plumbing and piping arrangements or where entry to all portions of the premises is not readily accessible for inspection purposes, making it impracticable or impossible to ascertain whether or not cross-connections exist. C. Type of Protection Required. 1. The type of protection that shall be provided to prevent backflow into the public water supply shall be commensurate with the degree of hazard that exists on the consumer's premises. The type of protective device that may be required (listing in an increasing level of protection) includes: double check valve assembly (DC), reduced pressure principle backflow prevention device (RP), and an air-gap separation (AG). The water user may choose a higher level of protection than required by the Water Company. The minimum types of backflow protection required to protect the public water system, at the user's water connections to premises with varying degrees of hazard, are given in Table 13.08.030. Situations which are not covered in Table 13.08.030 shall be evaluated on a case by case basis and the appropriate backflow protection shall be determined by the Water Company. Table 13.08.030 TYPE OF BACKFLOW PROTECTION REQUIRED Degree of Hazard | Minimum Type of Backflow Prevention A. Sewage and Hazardous Substances. 1. Premises where the public water system is used to supplement the reclaimed water supply | AG 2. Premises where there are wastewater pumping and/or treatment plants and there is no interconnection with the potable public water system. This does not include a single-family residence that has a sewage lift pump. An RP may be provided in lieu of an AG if approved by the Health Agency and the Water Company: | AG 3. Premises where reclaimed water is used and there is no interconnection with the potable public water system. An RP may be provided in lieu of an AG if approved by the Health Agency and the Water Company: | AG 4. Premises where hazardous substances are handled in any manner in which the substances may enter a potable public water system. This does not include a single family residence that has a sewage lift pump. An RP may be provided in lieu of an AG if approved by the Health Agency and the Water Company: | AG 5. Premises where there are irrigation systems into which fertilizers, herbicides, or pesticides are, or can be injected: | RP B. Auxiliary Water Supplies. 1. Premises where there is an unapproved auxiliary water supply which is inter-connected with the public water system. An RP or DC may be provided in lieu of an AG if approved by the Health Agency and the Water Company: | AG 2. Premises where there is an unapproved auxiliary water supply and there are no interconnections with the public water system. A DC may be provided in lieu of an RP if approved by the Health Agency and the Water Company: | RP C. Fire Protection Systems. 1. Premises where the fire system is directly supplied from the public water system and there is an unapproved auxiliary water supply on or to the premises (not interconnected): | DC 2. Premises where the fire system is supplied from the public water system and interconnected with an unapproved auxiliary water supply. An RP may be provided in lieu of an AG if approved by the Health Agency and the Water Company: | AG 3. Premises where the fire system is supplied from the public water system and where either elevated storage tanks or fire pumps which take suction from the private reservoirs or tanks are used: | DC D. Dockside Watering Points and Marine Facilities. 1. Pier hydrants for supplying water to vessel for any purpose: | RP 2. Premises where there are marine facilities: | RP E. Premises where entry is restricted so that inspections for cross-connections cannot be made with sufficient frequency or on sufficient frequency or on sufficiently short notice to assure that cross-connections do not exist: | RP F. Premises where there is a repeated history of cross-connections being established or reestablished: | RP Two (2) or more services supplying water from different street mains to the same building, structure, or premises through which an interstreet main flow may occur, shall have at least a standard check valve on each water service to be located adjacent to, and on the property side, of the respective meters. Such check valves shall not be considered adequate if backflow protection is deemed necessary to protect the city's mains from pollution or contamination: in such cases the installation of approved backflow assemblies at such service connections shall be required.
(Prior code § 7452)
Ask a question about El Monte law
Corpus searches the El Monte sections it holds and shows the ones that match, with their citations. Free, no sign-in.