For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 11-715 — ADDITIONAL SMOKE CONTROL REQUIREMENTS

Fresno Municipal Code (Supp. No. 55, Update 1 (online June 23, 2026): codified through Ordinance No. 2026-019) · Fresno Municipal Code § 11-715

Corpus is an independent public-information project, not the official City of Fresno website. Stable reference: corpuslaw.us/code/e3a494f6-c3b0-418b-82b0-483ffa7d8473

SEC. 11-715. - ADDITIONAL SMOKE CONTROL REQUIREMENTS.

Existing air conditioning and ventilation systems may be used as part of the smoke-control system. Existing return air plenum and approved fiberglass air ducts may be used as part of the smoke-control system. A smoke exhaust system shall be designed in a manner that will prevent smoke from going from one room to another, except when two or more rooms are connected together by means of a permanent unobstructed opening at least 20 square feet with a minimum three feet dimension, then the rooms shall be considered as one room for the purpose of designing the smoke-control system.

(Added Ord. 2007-102, § 1, eff. 1-20-08).

Ask a question about Fresno law

Corpus searches the Fresno sections it holds and shows the ones that match, with their citations. Free, no sign-in.